Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 4/23/2009 | 4/24/2009 | 4/24/2009 | P | PASS |
Forrest France
|
|
|
SECOND VISIT for failed first inspection items completed today including retest of post indicator valve, retest for non-functional notification devices, testing for mag lock FA interconnection at the main entry doors, checked relocated 3rd floor manual pull stations, adjusted dB levels at ADA and staff restrooms, map at panel, and elevator controls, supervising station signals checked okay. Fire alarm permit finaled.
|
INSP-Final Inspection | 4/17/2009 | 4/20/2009 | 4/20/2009 | P | CANC |
Troy Cobbley
|
|
|
I spoke to TIm about rescheduling this inspection due to a conflict of interest.
|
INSP-Final Inspection | 4/10/2009 | 4/13/2009 | 4/13/2009 | P | CANC |
Forrest France
|
|
|
|
Telephone call | | | 3/25/2009 | | DONE |
|
|
|
Called Bret at Mountain Alarm and left a message asking for the status of the project.
|
Telephone call | | | 3/25/2009 | | DONE |
|
|
|
Bret called and stated that he thought the project had already been finaled. He is going to send a technician to the job to ensure the previous items have been addressed and will schedule for a final inspection in the comming week.
|
INSP-Final Inspection | 7/21/2008 | 7/21/2008 | 7/21/2008 | A | FAIL |
Forrest France
|
|
|
See annotations on approved plan set for locations of areas or items in need of correction including 3rd floor MP stations, dB levels at ADA bathrooms and one staff restroom, two non-functional notification devices, PIV tamper self restoring signal per note #7, fire alarm interconnection to the mag locks at the main entry/exit doors, provide map at the panel per review note #24. FACP batteries, phone lines, sd, HD at the mech. room, sprinkler riser supervision, elevator controls with the exception of hoistway devices and voltage monitoring all tested okay.
|
(F) Reprint permit | | | 6/13/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/13/2008 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 4/30/2008 | | 5/12/2008 | | PASS |
Kenneth R Roule
|
|
|
See fire alarm plan review notes.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/12/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 5/12/2008 | | 5/12/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 5/12/2008 | | DONE |
|
|
|
bret anderson at ###-#### - permit ready
|
Permit Ready to Issue | | | 5/12/2008 | | DONE |
|
|
|
|
Telephone call | | | 5/2/2008 | | DONE |
|
|
|
Called Brett Anderson 5-02-08 to let him know that there were no calc sheets in the file for the new NAC panels. Review was stopped. No further review completed.
|
Plan resubmittals received | | | 4/30/2008 | | |
|
|
|
Plan Modification: Received application and three folders of submittal info and sheets F0.0, F1.0, F1.1, F1.2, F2.0; taken to fire review
|
FIR-Aging Inspection | 12/10/2007 | 12/10/2007 | 12/10/2007 | | DEFR |
Forrest France
|
|
|
Work in progress, pending field inspection request.
|
Plan assigned to (Mike) | 6/12/2007 | | 6/21/2007 | | PASS |
|
|
|
6/21/2007 12:24:22 MWT - activity updated through activity FIRA22 from case FIR07-00524.
|
Alarm Plan Check | 6/15/2007 | | 6/21/2007 | | PASS |
|
|
|
Waiting for new set of plans no review conducted yet.
|
Plan assigned to (Mike) | 6/18/2007 | | 6/21/2007 | | PASS |
|
|
|
6/21/2007 12:24:22 MWT - activity updated through activity FIRA22 from case FIR07-00524.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/21/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 6/21/2007 | | 6/21/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/21/2007 | | |
|
|
|
spoke with jodi and informed of fees and permit ready
|
Permit Ready to Issue | | | 6/21/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/21/2007 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/15/2007 | | |
|
|
|
Stephanie Cobbley asked if I would not review these plans and return the plans for this project to her because they have identical problems as the Fairfield Inn project that just failed FIR07-00525. She is going to correct both plans at the same time and return these to me when they are ready. I agreed so long as she made the changes quickly and returned them to me quickly.
|
Application received | | | 6/12/2007 | | |
|
|
|
|
Case Summary | | | 6/12/2007 | | DONE |
|
|
|
|