ePlanReview 
Description
This fire alarm permit is to replace an existing Radionics D7112 with an addressable/conventional Radionics (Bosch) D7024 Fire Alarm Control Panel. The explanation for panel replacement is that elevator recall and shutdown requirements were not possible with the existing FACP and a new fire alarm control panel was required. The scope of work includes bring all areas of the buildings fire alarm system in compliance with current 2003 IFC. Including audible visual notification to be installed in several accessible rooms, the addition of several addressable modules, relays, smoke and heat detectors to initiate elevator recall and shutdown functions. The building is fully fire sprinklered and fire sprinkler and HVAC monitoring along with fire smoke damper operation shall be required. Several fire alarm zones will remain as originally installed and will be connected to a conventional board in the new FACP device compatibility is required. No Building Permit is associated with this work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection4/23/20094/24/20094/24/2009PPASS
DetailsForrest France
SECOND VISIT for failed first inspection items completed today including retest of post indicator valve, retest for non-functional notification devices, testing for mag lock FA interconnection at the main entry doors, checked relocated 3rd floor manual pull stations, adjusted dB levels at ADA and staff restrooms, map at panel, and elevator controls, supervising station signals checked okay. Fire alarm permit finaled.
INSP-Final Inspection4/17/20094/20/20094/20/2009PCANC
DetailsTroy Cobbley
I spoke to TIm about rescheduling this inspection due to a conflict of interest.
INSP-Final Inspection4/10/20094/13/20094/13/2009PCANC
DetailsForrest France
Telephone call  3/25/2009 DONE
Called Bret at Mountain Alarm and left a message asking for the status of the project.
Telephone call  3/25/2009 DONE
Bret called and stated that he thought the project had already been finaled. He is going to send a technician to the job to ensure the previous items have been addressed and will schedule for a final inspection in the comming week.
INSP-Final Inspection7/21/20087/21/20087/21/2008AFAIL
DetailsForrest France
See annotations on approved plan set for locations of areas or items in need of correction including 3rd floor MP stations, dB levels at ADA bathrooms and one staff restroom, two non-functional notification devices, PIV tamper self restoring signal per note #7, fire alarm interconnection to the mag locks at the main entry/exit doors, provide map at the panel per review note #24. FACP batteries, phone lines, sd, HD at the mech. room, sprinkler riser supervision, elevator controls with the exception of hoistway devices and voltage monitoring all tested okay.
(F) Reprint permit  6/13/2008 DONE
CHANGE STATUS TO (ISS)  6/13/2008 DONE
Plan assigned to (SAM)4/30/2008 5/12/2008 PASS
DetailsKenneth R Roule
See fire alarm plan review notes.
PLANS/APPL TAKEN TO FRONT DESK  5/12/2008  
Inspection Record Card- Fire5/12/2008 5/12/2008 DONE
DetailsPatricia Smith
Telephone call  5/12/2008 DONE
bret anderson at ###-#### - permit ready
Permit Ready to Issue  5/12/2008 DONE
Telephone call  5/2/2008 DONE
Called Brett Anderson 5-02-08 to let him know that there were no calc sheets in the file for the new NAC panels. Review was stopped. No further review completed.
Plan resubmittals received  4/30/2008  
Plan Modification: Received application and three folders of submittal info and sheets F0.0, F1.0, F1.1, F1.2, F2.0; taken to fire review
FIR-Aging Inspection12/10/200712/10/200712/10/2007 DEFR
DetailsForrest France
Work in progress, pending field inspection request.
Plan assigned to (Mike)6/12/2007 6/21/2007 PASS
6/21/2007 12:24:22 MWT - activity updated through activity FIRA22 from case FIR07-00524.
Alarm Plan Check6/15/2007 6/21/2007 PASS
Waiting for new set of plans no review conducted yet.
Plan assigned to (Mike)6/18/2007 6/21/2007 PASS
6/21/2007 12:24:22 MWT - activity updated through activity FIRA22 from case FIR07-00524.
PLANS/APPL TAKEN TO FRONT DESK  6/21/2007  
Ready for Issue
Inspection Record Card- Fire6/21/2007 6/21/2007 DONE
Telephone call  6/21/2007  
spoke with jodi and informed of fees and permit ready
Permit Ready to Issue  6/21/2007 DONE
Issue and Print Permit  6/21/2007 DONE
Miscellaneous action  6/15/2007  
Stephanie Cobbley asked if I would not review these plans and return the plans for this project to her because they have identical problems as the Fairfield Inn project that just failed FIR07-00525. She is going to correct both plans at the same time and return these to me when they are ready. I agreed so long as she made the changes quickly and returned them to me quickly.
Application received  6/12/2007  
Case Summary  6/12/2007 DONE