Permit Information
Permit NumberFIR07-00525
StatusFinaled
Name MOUNTAIN ALARM
Site Address 3300 S SHOSHONE ST
Project NameMarriott Fairfield Inn
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing Radionics D7112 with an addressable/conventional Radionics (Bosch) D7024 Fire Alarm Control Panel. The explanation for panel replacement is that elevator recall and shutdown requirements were not possible with the existing FACP and a new fire alarm control panel was required. The scope of work includes bring all areas of the buildings fire alarm system in compliance with current 2003 IFC. Including audible visual notification to be installed in several accessible rooms, the addition of several addressable modules, relays, smoke and heat detectors to initiate elevator recall and shutdown functions. The building is fully fire sprinklered and fire sprinkler and HVAC monitoring along with fire smoke damper operation shall be required. Several fire alarm zones will remain as originally installed and will be connected to a conventional board in the new FACP device compatibility is required. No Building Permit is associated with this work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/2/200711/5/200711/5/2007PPASS
DetailsForrest France
Required corrections have been verified for completion, final fire alarm inspection passed, permit finaled.
INSP-Final Inspection10/23/200710/25/200710/26/2007PFAIL
DetailsForrest France
See approved plans 1st floor for areas in need of repair including three SD to be relocated, strobes are not in sync at the pool room, fireman's hat needs to illuminate solid upon activation of the SD at the elevator lobby, need to test EOL, provide signals report at next inspection, noted corrections have been verified from the previous inspection.
(F) Reprint permit  10/10/2007 DONE
CHANGE STATUS TO (ISS)  10/10/2007 DONE
Plan assigned to (Mike)10/4/2007 10/9/2007 PASS
10/9/2007 08:37:43 MWT - activity updated through activity FIRA22 from case FIR07-00525.
Alarm Plan Check  10/9/2007 PASS
Fire Alarm Review 3rd
PLANS/APPL TAKEN TO FRONT DESK  10/9/2007  
Ready for Re-Issue
Inspection Record Card- Fire10/9/2007 10/9/2007 DONE
Telephone call  10/9/2007 DONE
t/c w stephanie cobbley at ###-#### - permit ready and fees given (could not reach bret anderson at ###-####)
Permit Ready to Issue  10/9/2007 DONE
Miscellaneous action  10/8/2007  
Received updated battery calculations and cutsheets as required late in the afternoon.
Telephone call  10/8/2007  
Called Stephanie Cobbley ###-#### Left Msg that battery calculations resubmitted do not reflect the changes shown on the plans. (177cd horn strobes used in hearing impared rooms)
Called Bret Anderson Mountain Alarm ###-#### Let him know that Calculations were not Correct for the changes made.
Case Summary  10/4/2007 DONE
Plan resubmittals received  10/4/2007  
Plan modification received: applications, three folders of submittal info and pages F0.0, F1.0, F1.1, F1.2, F2.0; taken to fire review
INSP-Final Inspection9/7/20079/7/20079/11/2007PDEFR
DetailsForrest France
See inspection comments completed 9/10.
INSP-Final Inspection9/5/20079/6/20079/10/2007ADEFR
DetailsForrest France
See inspection comments on 9/10.
INSP-Final Inspection9/7/20079/10/20079/10/2007AFAIL
DetailsForrest France
Approved plans must be on site per condition of the permit, also need to provide as-builts reflecting field modifications, visible notification appliances in the sleeping areas must meet NFPA 72 7.5.4.4.2., need to provide signage at the doors to the FACP, provide key for the lock at the PIV to enable testing, provide map at the panel. Panel batteries, AC loss, sprinkler monitoring(except PIV) tested okay, verifed signals recieved.
INSP-Final Inspection9/4/20079/5/20079/5/2007ACANC
DetailsForrest France
Overbooked
PLANS/APPL TAKEN TO FRONT DESK  6/21/2007  
Ready for Issue
Alarm Plan Check6/21/2007 6/21/2007 PASS
Fire Alarm Review 2nd
Inspection Record Card- Fire6/21/2007 6/21/2007 DONE
Telephone call  6/21/2007 DONE
spoke to jodi ###-#### and informed of fees and permit ready
Permit Ready to Issue  6/21/2007 DONE
Issue and Print Permit  6/21/2007 DONE
Plan assigned to (Mike)6/12/2007 6/21/2007 PASS
6/21/2007 08:47:45 MWT - activity updated through activity FIRA22 from case FIR07-00525.
Telephone call  6/18/2007  
gave plans back to customer for a re-submittal required
Plan resubmittals received  6/18/2007  
Miscellaneous action  6/15/2007  
Fax copy of fire alarm review to Mountain Alarm and take plans to front desk for return.
Telephone call  6/15/2007 DONE
t/c w darcie at mountain alarm at ###-#### - resubmittal required on this permit and ready to be picked up
Alarm Plan Check6/14/2007 6/14/2007 FAIL
Fire Alarm Review 1st
Telephone call  6/14/2007  
Called Stephanie Cobbley told her elevator smokes could not be on the same zone as the Corridor smoke detectors.
Case Summary  6/12/2007 DONE
Application received  6/12/2007