INSP-Final Inspection | 11/2/2007 | 11/5/2007 | 11/5/2007 | P | PASS |
Forrest France
|
|
|
Required corrections have been verified for completion, final fire alarm inspection passed, permit finaled.
|
INSP-Final Inspection | 10/23/2007 | 10/25/2007 | 10/26/2007 | P | FAIL |
Forrest France
|
|
|
See approved plans 1st floor for areas in need of repair including three SD to be relocated, strobes are not in sync at the pool room, fireman's hat needs to illuminate solid upon activation of the SD at the elevator lobby, need to test EOL, provide signals report at next inspection, noted corrections have been verified from the previous inspection.
|
(F) Reprint permit | | | 10/10/2007 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/10/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 10/4/2007 | | 10/9/2007 | | PASS |
|
|
|
10/9/2007 08:37:43 MWT - activity updated through activity FIRA22 from case FIR07-00525.
|
Alarm Plan Check | | | 10/9/2007 | | PASS |
|
|
|
Fire Alarm Review 3rd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/9/2007 | | |
|
|
|
Ready for Re-Issue
|
Inspection Record Card- Fire | 10/9/2007 | | 10/9/2007 | | DONE |
|
|
|
|
Telephone call | | | 10/9/2007 | | DONE |
|
|
|
t/c w stephanie cobbley at ###-#### - permit ready and fees given (could not reach bret anderson at ###-####)
|
Permit Ready to Issue | | | 10/9/2007 | | DONE |
|
|
|
|
Miscellaneous action | | | 10/8/2007 | | |
|
|
|
Received updated battery calculations and cutsheets as required late in the afternoon.
|
Telephone call | | | 10/8/2007 | | |
|
|
|
Called Stephanie Cobbley ###-#### Left Msg that battery calculations resubmitted do not reflect the changes shown on the plans. (177cd horn strobes used in hearing impared rooms)
Called Bret Anderson Mountain Alarm ###-#### Let him know that Calculations were not Correct for the changes made.
|
Case Summary | | | 10/4/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/4/2007 | | |
|
|
|
Plan modification received: applications, three folders of submittal info and pages F0.0, F1.0, F1.1, F1.2, F2.0; taken to fire review
|
INSP-Final Inspection | 9/7/2007 | 9/7/2007 | 9/11/2007 | P | DEFR |
Forrest France
|
|
|
See inspection comments completed 9/10.
|
INSP-Final Inspection | 9/5/2007 | 9/6/2007 | 9/10/2007 | A | DEFR |
Forrest France
|
|
|
See inspection comments on 9/10.
|
INSP-Final Inspection | 9/7/2007 | 9/10/2007 | 9/10/2007 | A | FAIL |
Forrest France
|
|
|
Approved plans must be on site per condition of the permit, also need to provide as-builts reflecting field modifications, visible notification appliances in the sleeping areas must meet NFPA 72 7.5.4.4.2., need to provide signage at the doors to the FACP, provide key for the lock at the PIV to enable testing, provide map at the panel. Panel batteries, AC loss, sprinkler monitoring(except PIV) tested okay, verifed signals recieved.
|
INSP-Final Inspection | 9/4/2007 | 9/5/2007 | 9/5/2007 | A | CANC |
Forrest France
|
|
|
Overbooked
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/21/2007 | | |
|
|
|
Ready for Issue
|
Alarm Plan Check | 6/21/2007 | | 6/21/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
Inspection Record Card- Fire | 6/21/2007 | | 6/21/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/21/2007 | | DONE |
|
|
|
spoke to jodi ###-#### and informed of fees and permit ready
|
Permit Ready to Issue | | | 6/21/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/21/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 6/12/2007 | | 6/21/2007 | | PASS |
|
|
|
6/21/2007 08:47:45 MWT - activity updated through activity FIRA22 from case FIR07-00525.
|
Telephone call | | | 6/18/2007 | | |
|
|
|
gave plans back to customer for a re-submittal required
|
Plan resubmittals received | | | 6/18/2007 | | |
|
|
|
|
Miscellaneous action | | | 6/15/2007 | | |
|
|
|
Fax copy of fire alarm review to Mountain Alarm and take plans to front desk for return.
|
Telephone call | | | 6/15/2007 | | DONE |
|
|
|
t/c w darcie at mountain alarm at ###-#### - resubmittal required on this permit and ready to be picked up
|
Alarm Plan Check | 6/14/2007 | | 6/14/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Telephone call | | | 6/14/2007 | | |
|
|
|
Called Stephanie Cobbley told her elevator smokes could not be on the same zone as the Corridor smoke detectors.
|
Case Summary | | | 6/12/2007 | | DONE |
|
|
|
|
Application received | | | 6/12/2007 | | |
|
|
|
|