Permit Information
Permit NumberFIR07-00534
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 4268 N SPRUCE MEADOW AVE
Project NameSINGLE FAMILY HOME
Customer Number 
ePlanReview 
Description
Scope of Work
This permit is to install a new Anti-freeze fire sprinkler system in an existing residential assisted living center per Idaho State Department of Health & Welfare Division of Facility Standards. R-4 occupancy will be used by this office as the closest requirement for this type of residential assisted living center home. No Building permit is associated with this work. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/20/20079/21/20079/21/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection9/19/20079/20/20079/20/2007PCANC
DetailsTroy Cobbley
Please call 1/2 hour prior to inspection. Brian is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection9/17/20079/17/20079/17/2007PFAIL
DetailsTroy Cobbley
The domestic bypass valve is not installed yet. The underground supply has not been flushed yet. The riser needs mounted to the wall. Adequate pipe stands need to be supplied at the riser. Pendant sprinkler heads are blocked by ceiling fans and light fixtures.Project is not ready for a final.
INSP-Final Inspection9/13/20079/14/20079/14/2007ACANC
DetailsTroy Cobbley
needs to be rescheduled per contractor
INSP-Final Inspection9/12/20079/13/20079/13/2007AFAIL
DetailsTroy Cobbley
The bell has not been installed yet. No inspection was performed will need to be rescheduled.
INSP-Final Inspection9/11/20079/12/20079/12/2007PCANC
DetailsTroy Cobbley
Please call 1/2 hour prior to inspection. Brian is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection9/10/20079/10/20079/10/2007PCANC
DetailsTroy Cobbley
Brian F is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in/Hydro7/26/20077/27/20077/27/2007PPASS
DetailsTroy Cobbley
The sprinkler piping is ok to cover. There are some minor corrections required which can be verified at the final. As-built drawings will be required prior to a final that reflect the changes in the pipe routing and the additional heads.
Inspection Record Card- Fire7/19/2007 7/19/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  7/19/2007 DONE
Permit Ready to Issue  7/19/2007 DONE
Telephone call  7/19/2007  
Called ###-#### and told Lilly need someone to come down to pick up fire review and inspection card because she already has plans and told her fees per plans are approved.
Issue and Print Permit  7/19/2007 DONE
Telephone call  7/18/2007 DONE
lft ms with lilly ###-#### that plans have been denied and can be picked up
Telephone call  7/18/2007 DONE
shilo picked up plans- they were denied
Sprinkler Plan Check7/17/2007 7/17/2007 PASS
Plans are approved by bryan Johnson
Case Summary  6/15/2007 DONE
Application received  6/15/2007  
Pending Assignment by SAM6/15/2007