INSP-Final Inspection | 7/26/2007 | 7/27/2007 | 7/27/2007 | A | PASS |
Forrest France
|
|
|
C/N items are completed, fire alarm permit finaled.
|
INSP-Final Inspection | 7/26/2007 | 7/26/2007 | 7/26/2007 | P | CANC |
Forrest France
|
|
|
No time available to complete this inspection.
|
INSP-Final Inspection | 7/25/2007 | 7/25/2007 | 7/25/2007 | P | PART |
Forrest France
|
|
|
Final pending as-built plans for field modifications, also need to test door holder interconnections when completed, provide updated map at the panel.
|
INSP-Final Inspection | 7/23/2007 | 7/24/2007 | 7/24/2007 | A | NR |
Forrest France
|
|
|
Project is not ready for inspection at this time due to fire sprinkler permit testing.
|
INSP-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 | P | FAIL |
Troy Cobbley
|
|
|
The releasing panel would not trip the valve. The required second permit for the two panel interconnecton was not called in and was not tested. I did test the some of the smoke detectors and all of the manual pulls. But this test really should be started over.
|
Plan assigned to (Mike) | 6/19/2007 | | 6/25/2007 | | PASS |
|
|
|
6/25/2007 09:36:32 MWT - activity updated through activity FIRA22 from case FIR07-00540.
|
Alarm Plan Check | 6/25/2007 | | 6/25/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/25/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 6/25/2007 | | 6/25/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/25/2007 | | DONE |
|
|
|
t/c w cathy at allied general fire ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/25/2007 | | |
|
|
|
|
Issue and Print Permit | | | 6/25/2007 | | |
|
|
|
|
Application received | | | 6/19/2007 | | |
|
|
|
|