Case Summary | | | 7/10/2007 | | |
|
|
|
|
INSP-Final Inspection | 6/25/2007 | 6/26/2007 | 6/27/2007 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The phone lines connected to the D928 dialer had been connected wrong. Dan and I worked with tech support to figure it out.
|
INSP-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 | A | FAIL |
Forrest France
|
|
|
Interconnection verified at hood #1, one notification device did not function.
|
INSP-Alarm Testing | 6/22/2007 | 6/25/2007 | 6/25/2007 | A | FAIL |
Forrest France
|
|
|
The horn/strobe device in the kitchen area failed to function properly upon alarm activation.
|
Plan assigned to (Mike) | 6/19/2007 | | 6/22/2007 | | PASS |
|
|
|
6/22/2007 13:46:43 MWT - activity updated through activity FIRA22 from case FIR07-00541.
|
Alarm Plan Check | 6/22/2007 | | 6/22/2007 | | PASS |
|
|
|
Fire Alarm Quick Permit Review 2nd. "Pass" See Review Comment Attached. Subject to Field Inspector Acceptance and Testing.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/22/2007 | | |
|
|
|
Ready for Issue - Double permit fee. Troy Cobbley reported that work has been completed before permit was issued.
|
Inspection Record Card- Fire | 6/22/2007 | | 6/22/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/22/2007 | | DONE |
|
|
|
spoke with dan and informed of fees and permit ready.
|
Permit Ready to Issue | | | 6/22/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/22/2007 | | DONE |
|
|
|
|
Alarm Plan Check | 6/20/2007 | | 6/20/2007 | | FAIL |
|
|
|
Fire Alarm Quick Permit "Fail" Applicant has not indicated the zone, addresses on where the two New Kitchen Hoods will be connected on the fire alarm riser. The submitted riser indicates one existing kitchen hood only.
|
Miscellaneous action | | | 6/20/2007 | | |
|
|
|
Received a new quick permit application with a riser. Riser does not include the new Kitchen Hoods.
|
Miscellaneous action | | | 6/20/2007 | | |
|
|
|
Fax copy of Quick Permit Failure to Alarm Vendor.
|
Application received | | | 6/19/2007 | | |
|
|
|
|
Telephone call | | | 6/18/2007 | | |
|
|
|
Called alarm vendor. Told person in the office I needed a riser showing where the new kitchen hoods will be monitored. (Zone or Address) The office person said they would relay the message to Dan Buccino
|