INSP-Final Inspection | 12/19/2007 | 12/20/2007 | 12/20/2007 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 12/13/2007 | 12/14/2007 | 12/14/2007 | P | CANC |
Troy Cobbley
|
|
|
The fire alarm systems ended up not being tested due to time constraints and tamper switch issues. Per Matt his plans show two tampers switches. Each sprinkler system actually has three existing valves that need monitored. The sprinkler contractor failed to install the floor control valves which is two additional tampers. A total of five tamper switches have not been installed. No testing has been performed. The phone line troubles showing the first part of the day have been repaired. As-builts will be required not resubmittals. An updated map will be required as well.
|
FIR-Aging Inspection | 10/25/2007 | 10/25/2007 | 10/25/2007 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
Inspection Record Card- Fire | 7/26/2007 | | 7/26/2007 | | DONE |
|
|
|
|
Telephone call | | | 7/26/2007 | | DONE |
|
|
|
left a message w/matt. will call again.
|
Telephone call | | | 7/26/2007 | | DONE |
|
|
|
spoke w/matt and informed of permit ready and fees.
|
Permit Ready to Issue | | | 7/26/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/26/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 7/19/2007 | | 7/25/2007 | | PASS |
|
|
|
7/25/2007 12:34:46 MWT - activity updated through activity FIRA22 from case FIR07-00629.
|
Alarm Plan Check | 7/25/2007 | | 7/25/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/25/2007 | | |
|
|
|
Ready For Issue
|
Case Summary | | | 7/19/2007 | | |
|
|
|
|
Application received | | | 7/19/2007 | | |
|
|
|
|