INSP-Final Inspection | 10/11/2007 | 10/11/2007 | 10/11/2007 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 10/10/2007 | 10/11/2007 | 10/11/2007 | A | PASS |
Troy Cobbley
|
|
|
Permit has been finaled after the fourth try.
|
INSP-Alarm Testing | 10/10/2007 | 10/10/2007 | 10/10/2007 | P | FAIL |
Troy Cobbley
|
|
|
The four access controled egress doors are not shown on the fire alarm plans. Per mike these can be shown on an as-built. The fire alarm contractor needs to provide updated asbuilts and test the doors and the a/v's.
|
INSP-Alarm Testing | 10/8/2007 | 10/9/2007 | 10/9/2007 | A | FAIL |
Troy Cobbley
|
|
|
Only three of the seven new duct smoke detectors were tested. All three were missing the foam filter on the sample tube and one was also missing the donut on the back side of the detector. All three units did shut down as required. The supervision of the new nac panel by the facp was tested and passed. The remaining duct smoke detectors need to be tested and the a/v's tested. The inspection was stopped due to the missing items and time constraints.
|
INSP-Alarm Testing | 10/4/2007 | 10/8/2007 | 10/8/2007 | A | FAIL |
Troy Cobbley
|
|
|
The first duct smoke detector tested did not shut down the unit. The second duct detector was mounted incorrectly. The test was stopped.
|
Plan assigned to (Mike) | 7/30/2007 | | 8/2/2007 | | PASS |
|
|
|
8/2/2007 09:43:11 MWT - activity updated through activity FIRA22 from case FIR07-00654.
|
Alarm Plan Check | 8/1/2007 | | 8/2/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/2/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 8/2/2007 | | 8/2/2007 | | DONE |
|
|
|
|
Telephone call | | | 8/2/2007 | | DONE |
|
|
|
t/c w john campbell at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/2/2007 | | DONE |
|
|
|
|
Issue permit | | | 8/2/2007 | | |
|
|
|
|
Case Summary | | | 7/30/2007 | | |
|
|
|
|
Application received | | | 7/30/2007 | | |
|
|
|
|