INSP-Final Inspection | 8/27/2007 | 8/27/2007 | 8/27/2007 | P | PASS |
Forrest France
|
|
|
Verified required corrections, noted changes to be made at data entry regarding descriptor for supervisory signals, inspection passed, permit finaled.
|
INSP-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 | P | FAIL |
Troy Cobbley
|
|
|
The duct smoke detectors are mounted on the long side of the rectrangular duct not the short side. The duct smoke detectors will need to be tested after they have been relocated. The sample tubes will need to be changed.
|
Issue and Print Permit | | | 8/6/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 7/30/2007 | | 8/3/2007 | | PASS |
|
|
|
8/3/2007 09:46:43 MWT - activity updated through activity FIRA22 from case FIR07-00658.
|
Alarm Plan Check | 8/3/2007 | | 8/3/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/3/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 8/3/2007 | | 8/3/2007 | | DONE |
|
|
|
|
Telephone call | | | 8/3/2007 | | DONE |
|
|
|
t/c w jeffifer emel at united electric ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/3/2007 | | DONE |
|
|
|
|
Case Summary | | | 7/30/2007 | | |
|
|
|
|
Application received | | | 7/30/2007 | | |
|
|
|
|