Case Summary | | | 6/24/2008 | | DONE |
|
|
|
|
Miscellaneous action | | | 4/28/2008 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 2/12/2008 | 2/12/2008 | 2/12/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm work passed final inspection, permit finaled.
|
INSP-Alarm Testing | 2/6/2008 | 2/7/2008 | 2/7/2008 | A | PASS |
Forrest France
|
|
|
Completed balance of fire alarm testing including initiation devices on the 3rd and 4th floors, dampers at all floors-(non-functional dampers at the west end floors 1-4 repaired while on site), elevator recall, EOL voltage, closure at one door repaired while on site, signals and account checked, and reinspected noted defficiencies from the previous day for compliance. Need to provide building map at the panel including all initiation devices and their locations per review notes and as discussed, fire alarm permit work approved for final.
|
INSP-Alarm Testing | 2/5/2008 | 2/6/2008 | 2/6/2008 | A | PART |
Forrest France
|
|
|
Corrections noted at the previous inspection including a/v and pull station locations and non-functional sounder bases at three rooms verified for completion. FACP phone lines, batteries, AC power, SD above panel, and first floor nac tested okay. Notification devices for the 1st thru 4th floors tested - noted lacking coverage at the first floor vending/ice room, dB above 110 at two public restrooms (corrected while on site), a/v at the maintenance managers office on the 3rd floor does not function, sounder bases at three rooms 236, 336,and 436 do not function on general alarm. Also tested initating devices for the 1st and 2nd floors (manual pull stations and SD's only). Need to provide access for visual inspection of FSD functionality at some areas. Still need to test 3rd and 4th floor alarm initiation, elevator recall at both cars, 3rd and 4th floor nac panels, and check account and signal reciept information.
|
INSP-Alarm Testing | 1/29/2008 | 1/30/2008 | 1/30/2008 | A | DEFR |
Forrest France
|
|
|
Talk to Rand with Alarm Star About the issues of A/V devices being to low. Pull stations to high and the wrong (CD) for the devices in th ADA rooms.KR
|
INSP-Alarm Testing | 1/28/2008 | 1/29/2008 | 1/29/2008 | A | FAIL |
Forrest France
|
|
|
See inspection notes per site visit completed by K. Roule.
|
FIR-Aging Inspection | 12/14/2007 | 12/14/2007 | 12/14/2007 | | DEFR |
Forrest France
|
|
|
Under construction, work in progress.
|
Plan assigned to (Mike) | 7/31/2007 | | 8/13/2007 | | PASS |
|
|
|
8/13/2007 13:05:49 MWT - activity updated through activity FIRA22 from case FIR07-00662.
|
Alarm Plan Check | 8/10/2007 | | 8/13/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/13/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 8/13/2007 | | 8/13/2007 | | DONE |
|
|
|
|
Telephone call | | | 8/13/2007 | | DONE |
|
|
|
left message w lisa for tim ezell at ###-#### - permit ready and no fees due
|
Permit Ready to Issue | | | 8/13/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/13/2007 | | DONE |
|
|
|
|
Case Summary | | | 7/31/2007 | | |
|
|
|
|
Application received | | | 7/31/2007 | | |
|
|
|
|