Permit Information
Permit NumberFIR07-00663
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 1908 N 13TH ST
Project NameASHLEY MANOR
Customer Number 
ePlanReview 
Description
Scope of Work: Overhead Only
Beginning from the supply side of the back flow device, (provided by others) Install a new fire sprinkler system through out the one story 2,450-ft/a assisted living home. System shall be equipped with an alarm initiating device and an outside alarm. The plans shall include coverage in the garage, closets, bathrooms and foyers as directed by the bldg. department. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is not attached a BLD permit.
08/16/07 Plan Review Comments:05/22/08 Revised Scope of Work: The underground was revised along with the calculations to omit a water meter as it was not required.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/13/200810/14/200810/14/2008APASS
DetailsForrest France
All corrections made per last inspection. KR
INSP-Final Inspection9/17/20089/18/20089/18/2008AFAIL
DetailsForrest France
Per contractor missing cold cavity protection, noted missing escutcheons, lacking tamper switches at the main control and backflow shutoff valves.
INSP-Sprinkler Rough-in/Hydro6/12/20086/12/20086/12/2008PPART
DetailsForrest France
Final pending system fire alarm interconnection.
INSP-Sprinkler Rough-in/Hydro6/2/20086/3/20086/3/2008APART
DetailsForrest France
Overhead hydrostatic testing completed satisfactory for the new system piping.
INSP-Sprinkler Rough-in5/29/20086/2/20086/2/2008APASS
DetailsTroy Cobbley
UG Flush and the forward flush passed.. I notified todd that the flow switch and tamper switches will need to be connected to the fire alarm system.
Issue and Print Permit  5/29/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  5/27/2008 DONE
DetailsCathy Brown
Inspection Record Card- Fire5/27/2008 5/27/2008 DONE
DetailsCathy Brown
Telephone call  5/27/2008 DONE
DetailsCathy Brown
tlk to shaun ramsey ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  5/27/2008 DONE
DetailsCathy Brown
Plan assigned to (SAM)5/15/2008 5/27/2008 PASS
DetailsCathy Brown
5/27/2008 11:25:13 CMB - activity updated through activity FIRA22 from case FIR07-00663.
Sprinkler Plan Check5/15/2008 5/22/2008 PASS
Details
Plans & Calculations are approved by Bryan Johnson
INSP-Sprinkler Rough-in5/15/20085/15/20085/15/2008PPART
DetailsForrest France
Okay to cover underground supply line. Agreed to accept as-built plans for the deletion of the meter due to dedicated fire service.
Plan resubmittals received  5/15/2008  
Plan Modification: Received five coipes of application, and sheet FP1; taken to fire review
INSP-Sprinkler Rough-in5/9/20085/9/20085/9/2008PFAIL
DetailsForrest France
UG fire supply line is not approved for cover due to missing meter installation per plan, depth of bury does not meet min. requirements adjacent to the foundation.
INSP-Sprinkler Rough-in/Hydro12/13/200712/13/200712/13/2007PPART
DetailsForrest France
Missing one head at the pantry, remainder of the OH rough-in is acceptable, riser is not yet built, need to provide cold cavity protection as detailed.
Issue and Print Permit  10/15/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  10/12/2007 DONE
Inspection Record Card- Fire10/12/2007 10/12/2007 DONE
Telephone call  10/12/2007 DONE
tlk to shawn ramsey ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  10/12/2007  
Sprinkler Plan Check10/5/2007 10/10/2007 PASS
Plans & Calculations are approved by Bryan Johnson
Miscellaneous action  10/8/2007 DONE
Approved Early Start request. See Doc attached.
Plan resubmittals received  10/5/2007  
Application received  8/1/2007  
Pending Assignment by SAM8/1/2007