INSP-Final Inspection | 9/24/2007 | 9/24/2007 | 9/24/2007 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Final Inspection | 9/20/2007 | 9/21/2007 | 9/21/2007 | P | NR |
Forrest France
|
|
|
Need NFPA 72 record of completion forms.
|
INSP-Alarm Testing | 9/5/2007 | 9/5/2007 | 9/6/2007 | P | PART |
Forrest France
|
|
|
Noted corrections have been made, fire alarm testing passed, final pending completion of the scope of work per building plans and removal of the old FACP no longer in service adjacent to the fire riser.
|
INSP-Alarm Testing | 9/4/2007 | 9/5/2007 | 9/5/2007 | A | CANC |
Forrest France
|
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|
INSP-Alarm Testing | 8/31/2007 | 9/4/2007 | 9/4/2007 | A | FAIL |
Forrest France
|
|
|
The SD at the new control panel is too close to an HVAC supply register, one duct detector has the sample tube installed backward, need to locate the inspectors test valve to enable testing of the sprinkler flow switch, the existing FACP if no longer in service shall be removed to prevent confusion, need to verify signals at the supervising station.
|
INSP-Alarm Testing | 8/30/2007 | 8/31/2007 | 8/31/2007 | A | CANC |
Forrest France
|
|
|
Overbooked
|
Plan assigned to (Mike) | 8/1/2007 | | 8/29/2007 | | PASS |
|
|
|
8/29/2007 12:31:49 MWT - activity updated through activity FIRA22 from case FIR07-00664.
|
Alarm Plan Check | | | 8/29/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/29/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 8/29/2007 | | 8/29/2007 | | DONE |
|
|
|
|
Telephone call | | | 8/29/2007 | | DONE |
|
|
|
t/c w sean delacey at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/29/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/29/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/23/2007 | | |
|
|
|
|
Alarm Plan Check | | | 8/6/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Miscellaneous action | | | 8/6/2007 | | |
|
|
|
Fax copy of failed alarm review to applicant Rocky Mountain Electric ###-#### and Alarm Vendor Rob Ahten Protex.
|
Telephone call | | | 8/6/2007 | | DONE |
|
|
|
t/c w tyler at rocky mountain electric ###-#### - permit needs to be picked up for resubmittal
|
Application received | | | 8/1/2007 | | |
|
|
|
|