Description
This fire alarm permit is to add a new NAC booster panel and modify the existing fire alarm panel and install new smoke detectors, duct smoke detectors and audible visual notification as shown in a basement tenant remodel project. Building permit BLD07-00292 is to remodel the basement (about 11,800 square feet) and the choir loft (about 1,950 square feet) of an existing church. Work is to include interior nonbearing walls, 3 restrooms accessible to the disabled, movable partitions, the structural support for movable partitions, a 1-hr corridor, steel structure support at door headers, grease hoods and ducts, gypsum board ceilings, gypsum board soffits, suspended acoustical ceilings, and finishes. The exterior ramp will be constructed under a future permit. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/28/2008 DONE
Plans takent to records for scanning
INSP-Final Inspection1/16/20081/17/20081/17/2008PPASS
DetailsForrest France
Balance of fire alarm permit work testing completed today, noted one air return grill at the sacrisity hall to be relocated away from an adjacent SD, address changes at two devices made while on site, will verifiy current map at the panel and relocated hvac at the building final, permit finaled.
CHANGE STATUS TO (ISS)  11/5/2007  
Fire Alarm Still Needs to be Finished in Construction Areas
INSP-Final Inspection10/29/200710/31/200710/31/2007PPART
DetailsForrest France
Items on correction notice verified for completion, fire alarm permit finaled.
INSP-Final Inspection10/25/200710/26/200710/26/2007PFAIL
DetailsForrest France
test fire alarm panel, found that batterys in for fire alarm panel were incorrect, plans show 2, 110 AH batterys the batterys on site were only 50 AH, need to put in corrected batterys. Halway by restrooms will need a smoke added due to change in the plans. Elevator does not recall, does'nt have recall capabilities, could not verify detector in elevator shaft no access. relocate detector in kitchen. per KR
Plan assigned to (Mike)8/2/2007 8/9/2007 PASS
8/9/2007 13:03:54 MWT - activity updated through activity FIRA22 from case FIR07-00670.
Alarm Plan Check8/8/2007 8/9/2007 PASS
Fire Alarm review 1st
PLANS/APPL TAKEN TO FRONT DESK  8/9/2007  
Ready for Issue
Telephone call  8/9/2007 DONE
t/c w bill litzbauer at ###-#### - permit ready and fees given
Inspection Record Card- Fire8/9/2007 8/9/2007 DONE
Permit Ready to Issue  8/9/2007 DONE
Issue and Print Permit  8/9/2007 DONE
Application received  8/2/2007