Permit Information
Permit NumberFIR07-00686
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 6651 W FRANKLIN RD
Project NameSW ID Advanced Care Hospital
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new manual and automatic fire alarm system with AFS monitoring, smoke control systems (AHU shutdown, damper and door release), elevator recall, and audible visual notification, (chimes) and nurse call supervision. Building permit BLD07-00274 is to construct a new 50,275 square foot, two story, steel framed advanced care hospital building and related site improvements. This building will contain administrative offices, a therapy gym, dining room, commercial kitchen and ambulance drive-thru on the first floor. The second floor contains forty patient rooms, a pharmacy, day room, staff break room and storage areas. First Floor: 29,425 sq. ft., Second Floor 20,850 sq. ft.. All construction shall be per the approved plans and attached comment list. Separate grading & site utilities permit issued under BLD07-00904. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/28/2008 DONE
Plans taken to records for scanning
INSP-Final Inspection1/18/20081/18/20081/18/2008PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/17/20081/17/20081/17/2008AFAIL
DetailsTroy Cobbley
As-builts are needed showing the additional devices and the devices deleted. Also need the nfpa 72 forms.
INSP-Alarm Testing1/14/20081/15/20081/15/2008ADONE
DetailsTroy Cobbley
See the city approved plans for items tested and deficiencies noted.
Inspection1/15/20081/15/20081/15/2008PFAIL
DetailsTroy Cobbley
1-15-2008 Fire alarm inspection: Checked 1st and 2nd floor notification appliances and all 2nd floor system detectors, patient room detectors, Induct detectors and duct smoke detectors this inspection should have finished the preliminary fire alarm testing. The following deficiencies need to be addressed.
1. 1st Floor Mechanical & Electrical rooms have beam construction additional detectors required.
2. Chimes not installed in exit stairways.
3. Add visual notification in 1st floor Work Room 1062.
4. Add smoke detector in storage closet 1063A
5. Add Visual Notification in 1st Floor ADL Room Suite 1027
6. Audible /Visual Notification Required in Men's & Women's Locker & Toilet Room 1019 & 1013
7. Relocate Notification Appliances in Room 1023 "Blocked" - Also Audible Level to Low in the Same Room "Should Make Chime Strobe"
INSP-Alarm Testing1/14/20081/14/20081/14/2008ADONE
DetailsTroy Cobbley
See the city approved plans for locations of devices tested and deficiencies found.
FIR-Aging Inspection1/4/20081/4/20081/4/2008 NR
DetailsTroy Cobbley
work is in progress
Inspection Record Card- Fire10/5/2007 10/5/2007 DONE
Telephone call  10/5/2007 DONE
t/c w kirk meyer at ###-#### - permit ready and no fees due
Permit Ready to Issue  10/5/2007 DONE
Issue and Print Permit  10/5/2007 DONE
Plan assigned to (Mike)8/7/2007 10/4/2007 PASS
10/4/2007 16:20:53 MWT - activity updated through activity FIRA22 from case FIR07-00686.
Alarm Plan Check  10/4/2007 PASS
Fire Alarm Review 2nd
PLANS/APPL TAKEN TO FRONT DESK  10/4/2007  
Ready for Issue
Plan resubmittals received  9/28/2007  
received 1 fire alarm permit application, 3 submittal information, and 3 copys of sheets 1-7 taken to Fire
Telephone call  8/28/2007  
gave plans to peter with simplex grinell resubmittal is required
Alarm Plan Check8/27/2007 8/27/2007 FAIL
Fire Alarm Review 1st
Miscellaneous action  8/27/2007  
Fax copy of fire alarm review to Alarm Vendor Simplex ###-#### Lea Electric ###-#### and the Engineer Bridges & Paxton ###-####
Telephone call  8/27/2007 DONE
left vm for kirk meyer at ###-#### - permit needs to be picked up for resubmittal
Application received  8/7/2007