Miscellaneous action | | | 4/28/2008 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 1/17/2008 | 1/17/2008 | 1/17/2008 | A | FAIL |
Troy Cobbley
|
|
|
As-builts are needed showing the additional devices and the devices deleted. Also need the nfpa 72 forms.
|
INSP-Alarm Testing | 1/14/2008 | 1/15/2008 | 1/15/2008 | A | DONE |
Troy Cobbley
|
|
|
See the city approved plans for items tested and deficiencies noted.
|
Inspection | 1/15/2008 | 1/15/2008 | 1/15/2008 | P | FAIL |
Troy Cobbley
|
|
|
1-15-2008 Fire alarm inspection: Checked 1st and 2nd floor notification appliances and all 2nd floor system detectors, patient room detectors, Induct detectors and duct smoke detectors this inspection should have finished the preliminary fire alarm testing. The following deficiencies need to be addressed.
1. 1st Floor Mechanical & Electrical rooms have beam construction additional detectors required.
2. Chimes not installed in exit stairways.
3. Add visual notification in 1st floor Work Room 1062.
4. Add smoke detector in storage closet 1063A
5. Add Visual Notification in 1st Floor ADL Room Suite 1027
6. Audible /Visual Notification Required in Men's & Women's Locker & Toilet Room 1019 & 1013
7. Relocate Notification Appliances in Room 1023 "Blocked" - Also Audible Level to Low in the Same Room "Should Make Chime Strobe"
|
INSP-Alarm Testing | 1/14/2008 | 1/14/2008 | 1/14/2008 | A | DONE |
Troy Cobbley
|
|
|
See the city approved plans for locations of devices tested and deficiencies found.
|
FIR-Aging Inspection | 1/4/2008 | 1/4/2008 | 1/4/2008 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
Inspection Record Card- Fire | 10/5/2007 | | 10/5/2007 | | DONE |
|
|
|
|
Telephone call | | | 10/5/2007 | | DONE |
|
|
|
t/c w kirk meyer at ###-#### - permit ready and no fees due
|
Permit Ready to Issue | | | 10/5/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/5/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 8/7/2007 | | 10/4/2007 | | PASS |
|
|
|
10/4/2007 16:20:53 MWT - activity updated through activity FIRA22 from case FIR07-00686.
|
Alarm Plan Check | | | 10/4/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/4/2007 | | |
|
|
|
Ready for Issue
|
Plan resubmittals received | | | 9/28/2007 | | |
|
|
|
received 1 fire alarm permit application, 3 submittal information, and 3 copys of sheets 1-7 taken to Fire
|
Telephone call | | | 8/28/2007 | | |
|
|
|
gave plans to peter with simplex grinell resubmittal is required
|
Alarm Plan Check | 8/27/2007 | | 8/27/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Miscellaneous action | | | 8/27/2007 | | |
|
|
|
Fax copy of fire alarm review to Alarm Vendor Simplex ###-#### Lea Electric ###-#### and the Engineer Bridges & Paxton ###-####
|
Telephone call | | | 8/27/2007 | | DONE |
|
|
|
left vm for kirk meyer at ###-#### - permit needs to be picked up for resubmittal
|
Application received | | | 8/7/2007 | | |
|
|
|
|