INSP-Final Inspection | 8/30/2007 | 8/30/2007 | 8/30/2007 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 8/29/2007 | 8/30/2007 | 8/30/2007 | A | PASS |
Forrest France
|
|
|
Required corrections verified, fire alarm testing passed.
|
INSP-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 | A | FAIL |
Troy Cobbley
|
|
|
The fire alarm contractor and I could not get the heat to come on. Per the hvac contractor the valve might be turned off and he also stated that he did not think that the hvac unit was wired to shut down immediately which I notified them was required. No test performed.
|
INSP-Final Inspection | 8/24/2007 | 8/24/2007 | 8/27/2007 | P | FAIL |
Forrest France
|
|
|
HVAC is not wired to the duct detector to enable shutdown of the unit.
|
Issue permit | | | 8/20/2007 | | |
|
|
|
|
Plan assigned to (Mike) | 8/8/2007 | | 8/17/2007 | | PASS |
|
|
|
8/17/2007 09:11:18 MWT - activity updated through activity FIRA22 from case FIR07-00690.
|
Alarm Plan Check | 8/17/2007 | | 8/17/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/17/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 8/17/2007 | | 8/17/2007 | | DONE |
|
|
|
|
Telephone call | | | 8/17/2007 | | DONE |
|
|
|
lft vm with jodi spencer ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 8/17/2007 | | DONE |
|
|
|
|
Application received | | | 8/8/2007 | | |
|
|
|
|