Permit Information
Permit NumberFIR07-00700
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 3214 E AMITY RD
Project Name 
Customer Number 
ePlanReview 
Description
Original Permitted Work Scope:
This existing bldg. is being modified to include a new 6”wet riser with a back flow device to serve through out the proposed spec warehouse space with future rack storage. The existing sprinkler system was earlier demolished and removed under a separate permit. (FIR07-00568) Any plans for a future rack system will have to be submitted for approval under a separate permit. This building is to be fully fire sprinklered. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-00569.
When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/9/200711/9/200711/9/2007APASS
DetailsForrest France
Complete foward flush,Test flow switch tamper switch and bell.Test connection to alarm panel.KR
INSP-Final Inspection11/8/200711/8/200711/8/2007PPART
DetailsForrest France
OH rough-in inspection passed, noted overhead door is located opposite from what is indicated on approved plan set.
Sprinkler Plan Check11/7/2007 11/7/2007 PASS
Plan modification submittal canceled and permit returned to Issued Status, based on telcon from Brooke, Commercial Fire. The Applicant requested we cancel the as-built plans and they will install in accordance with the previously issued plans. We will log that action in tidemark and change the permit back to ISS status and bill them the minimum Plan Modification review fee of $150
CHANGE STATUS TO (ISS)  11/7/2007 DONE
See notes in fire plan activity or any questions please call Sam R.
Plan resubmittals received  10/16/2007  
Received modification/as builts. Received three copies of application, hydraulic calcs, United Water flow sheet, product info and page FP-1; taken to fire review
Issue and Print Permit  10/12/2007  
PLANS/APPL TAKEN TO FRONT DESK  10/9/2007 DONE
Telephone call  10/9/2007  
lft ms with voice system brook ###-#### that permit and fees are ready to be picked up
Inspection Record Card- Fire10/9/2007 10/9/2007 DONE
Permit Ready to Issue  10/9/2007 DONE
Sprinkler Plan Check9/26/2007 10/2/2007 PASS
Plans are approved by Bryan Johnson
Plan resubmittals received  9/26/2007  
Received three copies of application and submittal packets, FP-1 and cut sheets; taken to fire review
Miscellaneous action  9/5/2007 DONE
Approved Early Start request. Copy attached.
Plan resubmittals received  8/31/2007  
received "3" sets of revisions (35) pages & "3" sheets of FP-1--plans taken to Scott Arellano
Case Summary  8/10/2007 DONE
Application received  8/10/2007  
Pending Assignment by SAM8/10/2007    
Plan assigned to (SAM)10/16/2007    
Sprinkler Plan Check10/16/2007   FAIL
These plans were denied for the following reasons but are not limited to just these reasons as a complete review of the plans and calculations could not be performed. Note this was a plan modification of a previously approved plan.
* The friction loss for a 4” Wilkins 350 flowing 696.9 gpm is 10 psi. Taking this into consideration, this system will not achieve the minimum requirement of 5% remaining supply. In-fact the system will be around -2.5 lb below the 0 mark. Please revise the plans and resubmit ASAP.
Upon request the denied set of plan may be retrieved from my office for salvage. Plans will be maintained for 5 business days.