Permit Information
Permit NumberFIR07-00704
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 3795 S DEVELOPMENT AVE Unit: 100
Project NameSYRINGA NETWORKS
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing non required fire alarm and sprinkler monitoring system and install a new addressable non required manual fire alarm system with full audible visual notification in a tenant space within the building. The new fire alarm panel will consist of sprinkler and suppression system monitoring installed in the switch gear and equipment room. New manual pull stations will be installed in the Syringa Network tenant space and in the common corridor exits. A smoke detector will be installed above the new FACP. 12-14-2007 Plan Modification - This plan modification includes removing the original Ansul suppression panel that was to be installed for suppression system releasing service and use the main building FACP and releasing "SRPPs" modules that are connected to the main building fire alarm system for fire suppression and sprinkler pre-action releasing service. All releasing service requirements will be initiated by the building fire alarm control panel. Additional fire suppression peripheral devices are now shown on the building floor plans and riser along with the suppression area smoke detectors that will be used for cross zoning and a double interlock pre-action system. - No building permit is associated with this work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/28/2008 DONE
Plans taken to records for scanning
INSP-Final Inspection2/25/20082/27/20082/28/2008PPASS
DetailsForrest France
Corrections verified for completion, final alarm testing passed, permit finaled.
INSP-Final Inspection2/13/20082/15/20082/15/2008PFAIL
DetailsForrest France
Completed test of new fire alarm panel. Found that strobes in corridors were not in-sync and existing strobes in hallways were at 79 inches. As per Sam no changes will need to be made to existing strobes.All other testing per permit Final.
FIR-Aging Inspection1/8/20081/8/20081/8/2008 DEFR
DetailsForrest France
Work in progress
(F) Reprint permit  12/19/2007 DONE
(F) Reprint permit  12/19/2007 DONE
CHANGE STATUS TO (ISS)  12/19/2007 DONE
picked up plan modification
Plan assigned to (Mike)12/13/2007 12/14/2007 PASS
12/14/2007 16:24:00 CMB - activity updated through activity FIRA22 from case FIR07-00704.
Alarm Plan Check12/14/2007 12/14/2007 PASS
DetailsMichael Timmerman
Fire Alarm Review 3rd
Telephone call  12/14/2007 DONE
Contacted Charlie Bayne of Simplex Grinnell ###-#### asked him to bring me the information on the SRPP panels and other suppression devices to be controlled by the FACP. I also asked Charlie for a legible fire alarm sheet 3, one that I can read. Due to no other plans are in line for review, I am allowing him time to bring me the corrections we will not be holding any other customers up.
Inspection Record Card- Fire12/14/2007 12/14/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/14/2007 DONE
Telephone call  12/14/2007 DONE
tlk to receptionist for charlie ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  12/14/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/14/2007 DONE
Ready for Re-Issue
Plan resubmittals received  12/13/2007  
Received application and two folders of submittal info and pages 1, 2, 3, 4, 5; taken to fire review
Alarm Plan Check  9/12/2007 PASS
Fire Alarm Review 1st
PLANS/APPL TAKEN TO FRONT DESK  9/12/2007  
Ready for Issue
Inspection Record Card- Fire9/12/2007 9/12/2007 DONE
Telephone call  9/12/2007 DONE
left vm for charlie bayne at ###-#### - permit ready and fees given
Permit Ready to Issue  9/12/2007 DONE
Issue and Print Permit  9/12/2007 DONE
Plan assigned to (Mike)8/13/2007 9/12/2007 PASS
9/12/2007 11:36:09 MWT - activity updated through activity FIRA22 from case FIR07-00704.
Plan resubmittals received  8/28/2007  
Miscellaneous action  8/27/2007  
picked up failed plans
Telephone call  8/23/2007 DONE
t/c w charlie bayne at ###-#### - permit needs to be picked up and re-submitted
Alarm Plan Check  8/23/2007 FAIL
Fire Alarm Review 1st - Information provided in submittals included wrong notification appliances used. Calculations all wrong. Resubmittal required.
Telephone call  8/22/2007  
Called alarm vendor Charlie Bayne with Simplex Grinnell ###-#### left message on voice mail. Have questions on suppression system and synchronization module submitted. I am waiting for his response. I may need to fail plans based on his reply.
Case Summary  8/13/2007 DONE
Application received  8/13/2007