Miscellaneous action | | | 4/28/2008 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 3/19/2008 | 3/20/2008 | 3/20/2008 | A | PASS |
Forrest France
|
|
|
Corrections are complete, will verify plastic at unit smoke alarms is removed prior to building permit final. Fire alarm permit finaled.
|
INSP-Final Inspection | 3/18/2008 | 3/18/2008 | 3/19/2008 | P | FAIL |
Forrest France
|
|
|
Need to relocate smoke alarms at four locations including units 305,105, 102 and 203, also need to remove plastic at all apartment unit smoke alarms prior to occupancy.
|
INSP-Final Inspection | 3/10/2008 | 3/13/2008 | 3/14/2008 | A | PART |
Forrest France
|
|
|
Completed new fire alarm system testing for the networked panel, interconnection to building one, phase two sprinkler system monitoring, notification appliances for the basement parking garage, and elevator monitoring/recall. Common corridors and apartment units not tested at this time, noted wall mounted horn locations are not in compliance with NFPA 72 2002 7.4.6.1- see also fire code review note #28, elevator fire doors at some floors are not adjusted or missing smoke seals, the main entry door mag locks failed to drop out on alarm condition.
|
INSP-Supply line flush | 3/10/2008 | 3/13/2008 | 3/13/2008 | A | CANC |
Forrest France
|
|
|
bill Phone #: ###-####
|
Issue permit | | | 3/10/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/5/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 3/5/2008 | | 3/5/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/5/2008 | | DONE |
|
|
|
left vm for bret anderson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/5/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/29/2008 | | |
|
|
|
Plan modification accepted; received application and two folders with submittal info and plan sheets F0.0, F1.0, F1.1, F1.2, F1.3, F1.4, F1.5, F2.0; taken to fire plan review
|
INSP-Conference | 2/25/2008 | 2/25/2008 | 2/25/2008 | P | DONE |
Forrest France
|
|
|
Regarding project inspections.
|
FIR-Aging Inspection | 1/9/2008 | 1/9/2008 | 1/9/2008 | | DEFR |
Forrest France
|
|
|
Construction underway, wip.
|
Issue and Print Permit | | | 9/6/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 8/16/2007 | | 9/5/2007 | | PASS |
|
|
|
9/5/2007 14:44:04 MWT - activity updated through activity FIRA22 from case FIR07-00710.
|
Alarm Plan Check | | | 9/5/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/5/2007 | | |
|
|
|
Ready For Issue
|
Inspection Record Card- Fire | 9/5/2007 | | 9/5/2007 | | DONE |
|
|
|
|
Telephone call | | | 9/5/2007 | | DONE |
|
|
|
left vm for jodi spencer at ###-#### - permit ready and no fees
|
Permit Ready to Issue | | | 9/5/2007 | | DONE |
|
|
|
|
Case Summary | | | 8/16/2007 | | DONE |
|
|
|
|
Application received | | | 8/16/2007 | | |
|
|
|
|
Pending Assignment by SAM | 2/29/2008 | | | | |
|
|
|
|
Alarm Plan Check | 3/5/2008 | | | | PASS |
|
|
|
Plan Mod.
|