Permit Information
Permit NumberFIR07-00718
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 6401 S EISENMAN RD
Project NameQUARRY BUSINESS PARK CONDOS
Customer Number 
ePlanReview 
Description
Scope of Work - Modify the existing wet pipe system by adding 38 pendant and 4 upright heads to accommodate a new wall and ceiling. The existing up-right heads above the ceiling are to remain. This building is fully sprinklered and shall remain so. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-01239.
Re-Submittals Of The Following Items Are Required:
Provide calculations to support the revised head spacing which exceeds the original head spacing.
09/17/07 Calculations Provided - Provide calculations to support the addition of mechanical tees, and the Flex head assemblies submitted.
09/17/07 Additional equiv. feet added. - Sprig-ups 4'-0" or longer shall be restrained against lateral movement. Wire used for restraint shall be located within 2'-0" of a hanger. The hanger closest to a wire restraint shall be of a type that resists upward movement of a branch line. (NFPA 13-9.3.6.2, 9.3.6.5*, A.9.3.6.4) 09/17/07 Under Shell Permit Revise the TI cover sheet to reflect the actual spacing as it was submitted. The plans indicate a 14’-0” x 14’-0” layout. The cover sheet indicated a new layout of 120-ft/2. 09/17/07 Revised
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/200710/17/200710/17/2007APASS
DetailsTroy Cobbley
Permit finaled. The sprig ups into the overbuild areas are complete and match plans including the wire seismic supports. The insulation is at the roof deck. Forward flush of the backflow preventor passed.
INSP-Sprinkler Rough-in/Hydro9/19/20079/20/20079/20/2007APART
DetailsForrest France
Overhead rough-in is acceptable, no access provided to a janitors room-will verifiy at next visit, noted a hydrostatic test for this portion of the building has been completed,
INSP-Sprinkler Rough-in9/19/20079/19/20079/19/2007PCANC
DetailsForrest France
terry ###-#### Inspection cancelled from web by: John Warnick
Telephone call  9/19/2007 DONE
john at commercial fire ###-#### - permit ready and fees given
Permit Ready to Issue  9/19/2007 DONE
Issue and Print Permit  9/19/2007 DONE
Sprinkler Plan Check9/11/2007 9/18/2007 PASS
plans are approved as submitted by bryan johnson
PLANS/APPL TAKEN TO FRONT DESK  9/18/2007  
Inspection Record Card- Fire9/18/2007 9/18/2007 DONE
Plan resubmittals received  9/11/2007  
received "3" sets of calculations including the app. (32) pages & "3" sheets of FP-1- plans put on shelf for plan reviewer
Application received  8/17/2007  
Pending Assignment by SAM8/17/2007