INSP-Final Inspection | 2/6/2009 | 2/6/2009 | 2/6/2009 | P | PASS |
Forrest France
|
|
|
Fire alarm testing passed, permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 2/3/2009 | 2/5/2009 | 2/6/2009 | A | DONE |
Forrest France
|
|
|
Incorrect inspection type request-intended for fire alarm permit final.
|
FIR-Aging Inspection | 1/10/2008 | 1/10/2008 | 1/10/2008 | | DEFR |
Forrest France
|
|
|
wip
|
Issue and Print Permit | | | 9/13/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/11/2007 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/6/2007 | | PASS |
|
|
|
Revised plans; reviewed on site; approved subject to annotation for hallway strobe to be relocated or changed from 15 cd to 30 cd.
|
Alarm Plan Check | | | 8/29/2007 | | FAIL |
|
|
|
Need to extend strobe coverage upgrade throught the Diffusion Bay 125A and show/verify coverage in adjacent spaces open to the Bay.
|
Application received | | | 8/28/2007 | | DONE |
Mary Froemke
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 8/28/2007 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|