Permit Information
Permit NumberFIR07-00759
StatusFinaled
Name SUPERIOR ELECTRIC CONTRACTORS INC
Site Address 2626 S GEKELER LN
Project NameLAKEWOOD MONTESORRI SCHOOL
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing fire alarm control panel, add manual pull stations, audible visual notification and automatic smoke detection as required for daycares. Building permit BLD07-01372 is to remodel the existing 13,693 sq.ft. Montessori School Child Care Facility (established under MIS04-00176, C.O. #10272) by removing existing offices, kitchen and meeting areas; too create two new classrooms and support areas; reconfigure bathrooms to serve new classrooms; add new exterior doors such that all classrooms have exits directly to exterior; create two new office areas, an Art Room and Library; change the use of the sanctuary into an indoor exercise area. Scope of work will not increase existing building area or occupancy use group per the original certificate of occupancy of 8/31/04, but it will change the total occupant load. All per approved plans, zoning ordinance, central district health and licensing requirements of Boise City Clerk. Project reviewed as a Non-Separated Mixed Use Occupancy, the "B" occupancy used as allowable area control. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/28/2008 DONE
Plans taken to records to be scanned.
INSP-Final Inspection4/7/20084/8/20084/8/2008APASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection2/12/20082/12/20082/12/2008PDEFR
DetailsForrest France
Work in progress to amend items on the correction notice issued 12/28/07.
INSP-Final Inspection12/28/200712/28/200712/28/2007PFAIL
DetailsForrest France
Relocate SD at classroom #1 too close to HVAC diffuser, relocate one manual pull station at the SW exit door from the sanctuary that is too high, add notification devices at the faculty lounge and room 128 in use as an "art room", need to demo the old FACP, provide covers at two open junction boxes classroom #3, provide signage at the door to the FACP, post a current map at the panel including correct FACP, smoke and nac panel locations, see fire code review notes items #24 and #5 for knox box requirement and HVAC information regarding possible duct smoke detection required.
Issue and Print Permit  12/3/2007 DONE
Telephone call  11/27/2007  
Called and talked to superior electric office person and let her know that the plans have been ready for pickup for about a month now.
Plan assigned to (Mike)9/4/2007 11/1/2007 PASS
11/1/2007 11:31:23 MWT - activity updated through activity FIRA22 from case FIR07-00759.
Alarm Plan Check11/1/2007 11/1/2007 PASS
Fire Alarm Review 2nd
PLANS/APPL TAKEN TO FRONT DESK  11/1/2007  
Ready for Issue
Inspection Record Card- Fire11/1/2007 11/1/2007 DONE
Telephone call  11/1/2007 DONE
left vm for todd holbrook at ###-#### permit ready and fees given
Permit Ready to Issue  11/1/2007 DONE
Plan resubmittals received  10/31/2007  
Telephone call  9/13/2007 DONE
left message w lacey for todd holbrook at ###-#### - permit needs to be picked up and resubmitted
Alarm Plan Check  9/12/2007 FAIL
Fire Alarm Review 1st
Miscellaneous action  9/12/2007  
Fax Copy of Review to Alarm Vendor and Installer
Miscellaneous action  9/12/2007  
Double permit fee to be applied! Work completed before plans were reviewed.
Case Summary  9/4/2007 DONE
Application received  9/4/2007