Miscellaneous action | | | 4/28/2008 | | DONE |
|
|
|
Plans taken to records to be scanned.
|
INSP-Final Inspection | 4/7/2008 | 4/8/2008 | 4/8/2008 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
FIR-Aging Inspection | 2/12/2008 | 2/12/2008 | 2/12/2008 | P | DEFR |
Forrest France
|
|
|
Work in progress to amend items on the correction notice issued 12/28/07.
|
INSP-Final Inspection | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | FAIL |
Forrest France
|
|
|
Relocate SD at classroom #1 too close to HVAC diffuser, relocate one manual pull station at the SW exit door from the sanctuary that is too high, add notification devices at the faculty lounge and room 128 in use as an "art room", need to demo the old FACP, provide covers at two open junction boxes classroom #3, provide signage at the door to the FACP, post a current map at the panel including correct FACP, smoke and nac panel locations, see fire code review notes items #24 and #5 for knox box requirement and HVAC information regarding possible duct smoke detection required.
|
Issue and Print Permit | | | 12/3/2007 | | DONE |
|
|
|
|
Telephone call | | | 11/27/2007 | | |
|
|
|
Called and talked to superior electric office person and let her know that the plans have been ready for pickup for about a month now.
|
Plan assigned to (Mike) | 9/4/2007 | | 11/1/2007 | | PASS |
|
|
|
11/1/2007 11:31:23 MWT - activity updated through activity FIRA22 from case FIR07-00759.
|
Alarm Plan Check | 11/1/2007 | | 11/1/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/1/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 11/1/2007 | | 11/1/2007 | | DONE |
|
|
|
|
Telephone call | | | 11/1/2007 | | DONE |
|
|
|
left vm for todd holbrook at ###-#### permit ready and fees given
|
Permit Ready to Issue | | | 11/1/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/31/2007 | | |
|
|
|
|
Telephone call | | | 9/13/2007 | | DONE |
|
|
|
left message w lacey for todd holbrook at ###-#### - permit needs to be picked up and resubmitted
|
Alarm Plan Check | | | 9/12/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Miscellaneous action | | | 9/12/2007 | | |
|
|
|
Fax Copy of Review to Alarm Vendor and Installer
|
Miscellaneous action | | | 9/12/2007 | | |
|
|
|
Double permit fee to be applied! Work completed before plans were reviewed.
|
Case Summary | | | 9/4/2007 | | DONE |
|
|
|
|
Application received | | | 9/4/2007 | | |
|
|
|
|