INSP-Final Inspection | 12/18/2007 | 12/19/2007 | 12/19/2007 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 | A | FAIL |
Troy Cobbley
|
|
|
I arrived at the scheduled 8:00am and found tim but no heating guy. I left and returned at 11:45am. After testing four of the five duct smoke detectors in the open sales area, one duct detector was found inoperative. The test was stopped due to time constraints.
|
INSP-Final Inspection | 11/26/2007 | 11/27/2007 | 11/27/2007 | A | FAIL |
Troy Cobbley
|
|
|
The duct smoke detectors still need to be tested. Per tim not all of the units are shutting down upon detection of smoke. The notification circuits have been repaired and tested. The smoke detectors located over the nac panels have been relocated to the deck and tested.
|
INSP-Alarm Testing | 11/15/2007 | 11/20/2007 | 11/20/2007 | A | DONE |
Troy Cobbley
|
|
|
The alarm at the garden center dry system has been repaired. The secondary phone line trouble restoral has been repaired. The audio/visual have been tested. Not all of the exterior tenant devices are operating. The audio/visual at the north east entrance is not operating. The a/v in the bakery needs relocated as per the plan. I need to spot check the high ceiling a/v's to verify candella compliance. The smoke detectors over the nac panels need located per code at the deck as discussed and tested. None of the duct smoke detectors were tested since the contractor did not have smoke. One hvac unit at the very west end of the store does not have a duct smoke detector as shown on the plans. The duct detectors in the outside tenants are not installed either. As-builts are required.
|
INSP-Alarm Testing | 11/15/2007 | 11/19/2007 | 11/19/2007 | A | DONE |
Troy Cobbley
|
|
|
Need to test all audio/visuals, test duct smoke detectors and the flow alarm on the new dry pipe vavle did not sen a signal to the facp. I also need a print out of todays signals for verification.
|
INSP-Alarm Testing | 11/15/2007 | 11/16/2007 | 11/16/2007 | A | DONE |
Troy Cobbley
|
|
|
The ham hood system came in and went out correctly. The phone lines also tested ok. But the phone line troubles do not annunciate audibly at the annunciators and the zone descriptors for the NAC panels is not correct. Battery troubles do not annunciate at the panel either. I believe its a D113 module that needs to be added based on past experiences. This is all that was tested today.
|
Issue and Print Permit | | | 10/8/2007 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/4/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/4/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 10/4/2007 | | 10/4/2007 | | DONE |
|
|
|
|
Telephone call | | | 10/4/2007 | | DONE |
|
|
|
t/c w tim morgan at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/4/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 9/6/2007 | | 10/4/2007 | | PASS |
|
|
|
10/4/2007 09:34:04 MWT - activity updated through activity FIRA22 from case FIR07-00770.
|
Telephone call | | | 10/3/2007 | | |
|
|
|
Called Alarm Designer Asked for Data Sheets on Batteries to be Used in the Fire Alarm System.
|
Miscellaneous action | | | 10/2/2007 | | DONE |
|
|
|
faxed early start request requirements to Tim Morgan, ###-#### (fax) at his request (ph ###-####)
|
Plan resubmittals received | | | 9/27/2007 | | |
|
|
|
|
Telephone call | | | 9/18/2007 | | DONE |
|
|
|
gave plans back to summit security systems--resubmittal required
|
Alarm Plan Check | | | 9/17/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Telephone call | | | 9/17/2007 | | DONE |
|
|
|
left vm for tim morgan at ###-#### - permit needs to be picked up and resubmitted
|
Miscellaneous action | | | 9/17/2007 | | |
|
|
|
Fax copy of Review to Applicant Tim Morgan ###-#### and Design Person Gordon Rice Asset Protection ###-####
|
Case Summary | | | 9/6/2007 | | DONE |
|
|
|
|
Application received | | | 9/6/2007 | | |
|
|
|
|