INSP-Final Inspection | 10/26/2009 | 10/26/2009 | 10/26/2009 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 11/29/2007 | 11/30/2007 | 11/30/2007 | P | PART |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 11/29/2007 at 5:00:15 PM. Contact: ###-####. Noted two pendent heads at the east side have been changed to QR as discussed. Sprinkler final pending removal of tape at covered uprights and escutcheons at hard lid ceilings when painting and sheetrock patching is completed. Contact phone number is incorrect, line has been disconnected.
|
INSP-Sprinkler Rough-in | 9/19/2007 | 9/20/2007 | 9/21/2007 | A | PART |
Forrest France
|
|
|
Two existing standard response heads at the east corner need to be QR type matching the new heads installed in the same fire area, also missing hangers at five arm-overs to new pendent heads, see plans for annotations, rough-in approved for cover pending corrections.
|
Telephone call | | | 9/11/2007 | | DONE |
|
|
|
Spoke with Phoenix fire and they will resubmit a larger scale floor plan and describe the scope of work in detail.
|
Plan resubmittals received | | | 9/11/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/11/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/11/2007 | | 9/11/2007 | | PASS |
|
|
|
|
Inspection Record Card- Fire | 9/11/2007 | | 9/11/2007 | | DONE |
|
|
|
|
Telephone call | | | 9/11/2007 | | DONE |
|
|
|
left message w michelle for trent bice at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 9/11/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/11/2007 | | DONE |
|
|
|
|
Application received | | | 9/7/2007 | | |
|
|
|
|
Sprinkler Plan Check | 9/7/2007 | | 9/7/2007 | | FAIL |
|
|
|
Faxed resubmittal items to Trent Bice. Application was incomplete.
|
Application DENIED | | | 9/7/2007 | | DONE |
|
|
|
|
Pending Assignment by SAM | 9/7/2007 | | | | |
|
|
|
|