INSP-Final Inspection | 11/27/2007 | 11/27/2007 | 11/27/2007 | P | PASS |
Troy Cobbley
|
|
|
overhead finaled, new set of city approved plans on site with all changesmade and approved..Per KR
|
Issue permit | | | 11/27/2007 | | |
|
|
|
|
Plan assigned to (SAM) | 11/21/2007 | | 11/26/2007 | | PASS |
|
|
|
11/26/2007 15:07:53 CMC - activity updated through activity FIRA22 from case FIR07-00782.
|
Sprinkler Plan Check | 11/21/2007 | | 11/26/2007 | | PASS |
|
|
|
Note:
This was the third review. This review was the result of a plan modification where a total of twelve heads including the remote area calculated were affected. Plans are Approved by Bryan
Johnson
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/26/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/26/2007 | | 11/26/2007 | | DONE |
|
|
|
|
Telephone call | | | 11/26/2007 | | DONE |
|
|
|
lft vm with trent bice 468 that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 11/26/2007 | | |
|
|
|
|
Plan resubmittals received | | | 11/21/2007 | | |
|
|
|
Modification to plan submitted. Received transmittal, and four copies of application, hydraulic calcs, and page 2 of 2; taken to fire review
|
INSP-Sprinkler Rough-in/Hydro | 11/16/2007 | 11/16/2007 | 11/16/2007 | A | FAIL |
Troy Cobbley
|
|
|
Overhead hydro test passed. The doghouses need inspected still. One head needs to be added between the two kitchen hoods. Two heads need to be extended in the north dining area to provide coverage under a soffit/decorative beam. Sprinkler coverage needs to be added in the new shed that is attached to the main building. The sprinkler contractor needs to contact Brian about installing galvanized piping on the roof of the structure for the additional dog house and the addition of the sprinkler head in the shed.
|
Issue and Print Permit | | | 10/15/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/3/2007 | | DONE |
|
|
|
|
Telephone call | | | 10/3/2007 | | DONE |
|
|
|
tlk to trent bide ###-#### that permit and fees are ready to be picked up
|
Inspection Record Card- Fire | 10/3/2007 | | 10/3/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/3/2007 | | |
|
|
|
|
Sprinkler Plan Check | 9/27/2007 | | 10/1/2007 | | PASS |
|
|
|
Plans are approved with conditions by Bryan Johnson
|
Plan resubmittals received | | | 9/27/2007 | | |
|
|
|
|
Application received | | | 9/12/2007 | | |
|
|
|
|
Pending Assignment by SAM | 9/12/2007 | | | | |
|
|
|
|