Permit NumberFIR07-00782
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 7751 W SPECTRUM ST
Project Name
Customer Number 
ePlanReview 
Description
Scope of Work: Overhead
The overhead fire sprinkler scope of work includes installing a 3" wet riser to serve through out the heated areas and an Anti-Freeze Loop system to serve through out the exterior dining section and the cold attic spaces. Central BB1 Attic heads along the roof line in the attic. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD07-01261& UG permit FIR07-00756..
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/27/200711/27/200711/27/2007PPASS
DetailsTroy Cobbley
overhead finaled, new set of city approved plans on site with all changesmade and approved..Per KR
Issue permit  11/27/2007  
Plan assigned to (SAM)11/21/2007 11/26/2007 PASS
11/26/2007 15:07:53 CMC - activity updated through activity FIRA22 from case FIR07-00782.
Sprinkler Plan Check11/21/2007 11/26/2007 PASS
Note:
This was the third review. This review was the result of a plan modification where a total of twelve heads including the remote area calculated were affected. Plans are Approved by Bryan
Johnson
PLANS/APPL TAKEN TO FRONT DESK  11/26/2007 DONE
Inspection Record Card- Fire11/26/2007 11/26/2007 DONE
Telephone call  11/26/2007 DONE
lft vm with trent bice 468 that permit and fees are ready to be picked up
Permit Ready to Issue  11/26/2007  
Plan resubmittals received  11/21/2007  
Modification to plan submitted. Received transmittal, and four copies of application, hydraulic calcs, and page 2 of 2; taken to fire review
INSP-Sprinkler Rough-in/Hydro11/16/200711/16/200711/16/2007AFAIL
DetailsTroy Cobbley
Overhead hydro test passed. The doghouses need inspected still. One head needs to be added between the two kitchen hoods. Two heads need to be extended in the north dining area to provide coverage under a soffit/decorative beam. Sprinkler coverage needs to be added in the new shed that is attached to the main building. The sprinkler contractor needs to contact Brian about installing galvanized piping on the roof of the structure for the additional dog house and the addition of the sprinkler head in the shed.
Issue and Print Permit  10/15/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  10/3/2007 DONE
Telephone call  10/3/2007 DONE
tlk to trent bide ###-#### that permit and fees are ready to be picked up
Inspection Record Card- Fire10/3/2007 10/3/2007 DONE
Permit Ready to Issue  10/3/2007  
Sprinkler Plan Check9/27/2007 10/1/2007 PASS
Plans are approved with conditions by Bryan Johnson
Plan resubmittals received  9/27/2007  
Application received  9/12/2007  
Pending Assignment by SAM9/12/2007