INSP-Final Inspection | 12/12/2007 | 12/12/2007 | 12/12/2007 | P | PASS |
Forrest France
|
|
|
All corrections made,per last inspection notes. KR
|
INSP-Final Inspection | 12/4/2007 | 12/6/2007 | 12/6/2007 | A | FAIL |
Forrest France
|
|
|
Missing caps at the FDC, need to remove the allen wrench from the flow switch at the main riser and replace the cover ASAP, provide a current annual inspection for the existing system, need resubmitted plans available on site at the next inspection.
|
Issue and Print Permit | | | 11/7/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/6/2007 | | 11/6/2007 | | DONE |
|
|
|
|
Telephone call | | | 11/6/2007 | | DONE |
|
|
|
tlk to shawn ramsey ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 11/6/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/2/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/24/2007 | | 10/31/2007 | | PASS |
|
|
|
This was a review of a previously approved plan which affected 24 heads. This plan was submitted as a plan modification due to tenant build out by bryan johnson
|
INSP-Sprinkler Rough-in | 10/29/2007 | 10/30/2007 | 10/30/2007 | A | PART |
Forrest France
|
|
|
Okay for sheetrock install at the basement level and the first floor restrooms, contractor to comply with listed min. spacing requirements of the residential heads installed, noted possible light fixture obstructions due to close proximity of heads and electrical junction boxes at some locations, will need resubmitted plans at next inspection for verification of field mods.
|
Plan resubmittals received | | | 10/24/2007 | | |
|
|
|
received fire app (2) pages & letter of transmittal from debest, & "5" sets of plans-- plans put on fire shelf
|
Issue and Print Permit | | | 10/10/2007 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/9/2007 | | |
|
|
|
|
Telephone call | | | 10/9/2007 | | DONE |
|
|
|
tlk to shaun ramsey ###-#### that permit and fees are ready to be picked up
|
Inspection Record Card- Fire | 10/9/2007 | | 10/9/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/9/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/25/2007 | | 10/8/2007 | | PASS |
|
|
|
Plans approved as submitted by Bryan Johnson
|
Case Summary | | | 9/25/2007 | | |
|
|
|
|
Application received | | | 9/25/2007 | | |
|
|
|
|
Pending Assignment by SAM | 9/25/2007 | | | | |
|
|
|
|