INSP-Final Inspection | 8/11/2008 | 8/11/2008 | 8/11/2008 | A | PASS |
Forrest France
|
|
|
Final fire alarm inspection passed, remainder of devices tested, door closure at one location repaired while on site, field ceiling tile installation at the lab storage room to be verified prior to fire life safety approval. Fire alarm permit finaled.
|
INSP-Final Inspection | 8/7/2008 | 8/8/2008 | 8/11/2008 | A | DEFR |
Forrest France
|
|
|
Inspection scheduled 8/11 per discussion.
|
INSP-Alarm Testing | 6/10/2008 | 6/11/2008 | 6/11/2008 | A | PART |
Forrest France
|
|
|
See annotations on approved plan set for areas inspected and passed today including door holders, manual pull stations, SD's and HD's, noted areas not yet complete, one deleted SD, and overspaced smoke detectors at a common corridor.
|
INSP-Alarm Testing | 6/4/2008 | 6/5/2008 | 6/5/2008 | A | PART |
Forrest France
|
|
|
See areas marked on approved plan set for initiation and notification devices tested and okayed today including patient rooms, common corridor, and roof top AHU's.
|
INSP-Alarm Testing | 6/3/2008 | 6/4/2008 | 6/4/2008 | P | PART |
Forrest France
|
|
|
And we continue on with this one. Phone #: ###-#### Internet Inspection Request from: Scott Laws
|
INSP-Alarm Testing | 5/23/2008 | 5/28/2008 | 5/29/2008 | A | PART |
Forrest France
|
|
|
See approved plans for areas inspected today, noted smoke detectors at six patient rooms to be relocated, construction is still underway at some locations.KR
|
INSP-Alarm Testing | 5/28/2008 | 5/29/2008 | 5/29/2008 | A | PART |
Forrest France
|
|
|
See approved plans for areas inspected today. Noted smoke detectors at six patient rooms were relocated and tested as per Forrest notes, construction is still underway at some locations.
|
FIR-Aging Inspection | 1/22/2008 | 1/22/2008 | 1/22/2008 | | DEFR |
Forrest France
|
|
|
Construction underway, work in progress.
|
Inspection Record Card- Fire | 10/9/2007 | | 10/9/2007 | | DONE |
|
|
|
|
Telephone call | | | 10/9/2007 | | DONE |
|
|
|
t/c w larry geyer at ###-#### x 30 - permit ready and fees given
|
Permit Ready to Issue | | | 10/9/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/9/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 10/4/2007 | | 10/8/2007 | | PASS |
|
|
|
10/8/2007 15:41:45 MWT - activity updated through activity FIRA22 from case FIR07-00830.
|
Alarm Plan Check | | | 10/8/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/8/2007 | | |
|
|
|
Ready for Issue
|
Case Summary | | | 10/4/2007 | | DONE |
|
|
|
|
Application received | | | 10/4/2007 | | |
|
|
|
|