INSP-Final Inspection | 7/7/2008 | 7/7/2008 | 7/7/2008 | P | PASS |
Troy Cobbley
|
|
|
Kitchen hood fire system testing complete. KR
|
INSP-Final Inspection | 6/26/2008 | 6/27/2008 | 6/27/2008 | A | FAIL |
Forrest France
|
|
|
Exhaust fan shut down during test, fan shall remain on when system is tripped. Electrical power under hood did not shut off.All power under shall shut down. KR
|
FIR-Aging Inspection | 1/7/2008 | 1/7/2008 | 1/7/2008 | | NR |
Troy Cobbley
|
|
|
work is in progress per rod walters.
|
Application received | | | 10/5/2007 | | |
|
|
|
|
Issue and Print Permit | | | 10/5/2007 | | DONE |
|
|
|
|