INSP-Final Inspection | 3/31/2008 | 4/7/2008 | 4/7/2008 | P | PASS |
Forrest France
|
|
|
Complete remaining testing per Forrest notes from last inspection.KR
|
INSP-Final Inspection | 3/25/2008 | 3/26/2008 | 3/26/2008 | A | FAIL |
Forrest France
|
|
|
Prior to inspection the NFPA 72 "Inspection and testing" form Fig. 10.6.2.3 must be completed including a copy of the supervising station signals report- see fire code review notes #8, audible notification at the existing tenant URS is not temporal as required, provide key for elevator reset at the next inspection. Manual pull, SD at the panel, sprinkler monitoring, FACP phone lines, batteries, AC loss, and the duct detector tested okay, notification device locations for the first and second floors appear satisfactory. Elevator controls not tested at this tme.
|
FIR-Aging Inspection | 1/31/2008 | 1/31/2008 | 1/31/2008 | | DEFR |
Forrest France
|
|
|
Site work in progress, pending field inspection request.
|
Issue and Print Permit | | | 10/30/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 10/22/2007 | | 10/26/2007 | | PASS |
|
|
|
10/26/2007 09:49:08 MWT - activity updated through activity FIRA22 from case FIR07-00880.
|
Alarm Plan Check | 10/26/2007 | | 10/26/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/26/2007 | | |
|
|
|
Ready For Issue
|
Inspection Record Card- Fire | 10/26/2007 | | 10/26/2007 | | DONE |
|
|
|
|
Telephone call | | | 10/26/2007 | | DONE |
|
|
|
left message w rona for john lopez at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/26/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/24/2007 | | |
|
|
|
received "2" separate fire #'s with applications (2 pages), & "3" sets of plans -plans put on fire shelf
|
Alarm Plan Check | | | 10/23/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Miscellaneous action | | | 10/23/2007 | | |
|
|
|
Review faxed to Fire Alarm Applicant John Lopez Fire Sentry Systems. ###-####
|
Telephone call | | | 10/23/2007 | | DONE |
|
|
|
left message w thida for john lopez at ###-#### - permit needs to be picked up and resubmitted
|
Telephone call | | | 10/23/2007 | | |
|
|
|
gave plans to fire sentry systems resubmittal required
|
Application received | | | 10/22/2007 | | |
|
|
|
|