Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR07-00880
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1750 W FRONT ST
Project NameALSCOTT GROVE ST OFFICE
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new fire alarm panel and notification appliances in the first and second floor public & common use areas and provide audible visual notification in an existing tenant space URS. The new system includes sprinkler and valve tamper monitoring, elevator primary and alternate control, shunt trip, fire hat and shunt trip power monitoring. The new system requires a duct smoke detector installed in return air system of the building HVAC system, remote annunciator, manual pull station and smoke detector above the new FACP. Building permit BLD07-00991 is to remodel the front entrance vestibule and interior lobby area per approved plans & CZC07-00087. Work to include, changing out the existing sprinkler heads to quick response sprinklers in lieu of fire rating corridor, construction of new non-rated partition, installation of suspended ceiling and related lighting, miscellaneous related interior finishes. This building is fully fire sprinkled for one hour fire resistive substitution.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/31/20084/7/20084/7/2008PPASS
DetailsForrest France
Complete remaining testing per Forrest notes from last inspection.KR
INSP-Final Inspection3/25/20083/26/20083/26/2008AFAIL
DetailsForrest France
Prior to inspection the NFPA 72 "Inspection and testing" form Fig. 10.6.2.3 must be completed including a copy of the supervising station signals report- see fire code review notes #8, audible notification at the existing tenant URS is not temporal as required, provide key for elevator reset at the next inspection. Manual pull, SD at the panel, sprinkler monitoring, FACP phone lines, batteries, AC loss, and the duct detector tested okay, notification device locations for the first and second floors appear satisfactory. Elevator controls not tested at this tme.
FIR-Aging Inspection1/31/20081/31/20081/31/2008 DEFR
DetailsForrest France
Site work in progress, pending field inspection request.
Issue and Print Permit  10/30/2007 DONE
Plan assigned to (Mike)10/22/2007 10/26/2007 PASS
10/26/2007 09:49:08 MWT - activity updated through activity FIRA22 from case FIR07-00880.
Alarm Plan Check10/26/2007 10/26/2007 PASS
Fire Alarm Review 2nd
PLANS/APPL TAKEN TO FRONT DESK  10/26/2007  
Ready For Issue
Inspection Record Card- Fire10/26/2007 10/26/2007 DONE
Telephone call  10/26/2007 DONE
left message w rona for john lopez at ###-#### - permit ready and fees given
Permit Ready to Issue  10/26/2007 DONE
Plan resubmittals received  10/24/2007  
received "2" separate fire #'s with applications (2 pages), & "3" sets of plans -plans put on fire shelf
Alarm Plan Check  10/23/2007 FAIL
Fire Alarm Review 1st
Miscellaneous action  10/23/2007  
Review faxed to Fire Alarm Applicant John Lopez Fire Sentry Systems. ###-####
Telephone call  10/23/2007 DONE
left message w thida for john lopez at ###-#### - permit needs to be picked up and resubmitted
Telephone call  10/23/2007  
gave plans to fire sentry systems resubmittal required
Application received  10/22/2007