Permit NumberFIR07-00898
StatusFinaled
Name UNITED FIRE PROTECTION LLC
Site Address 5246 W OVERLAND RD
Project NameHILLCREST SHOPPING CNTR
Customer Number 
ePlanReview 
Description
overheadScope of Work:
Modify the existing wet system by adding and relocating sprinklers to accommodate a new wall and ceiling layout with in this new tenant space. The work will include plugging and removing the existing protection as indicated on the plans.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD07-01556.01/28/08 Revised Scope of Work:
The original scope of work was modified to include 5 additional heads located at the eves. The calculations were revised to include the revised water flow information dated 01/28/08. The revisions are noted as Revision #1 and dated 01/28/08. These modifications do not appear to adversely affect the performance of the system as it was originally approved.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/10/2009 DONE
Sent for archiving
INSP-Final Inspection2/14/20082/14/20082/14/2008PPASS
DetailsTroy Cobbley
permit finaled
PLANS/APPL TAKEN TO FRONT DESK  2/14/2008 DONE
Inspection Record Card- Fire2/14/2008 2/14/2008 DONE
DetailsCathy Brown
Telephone call  2/14/2008 DONE
tlk to ben chavez ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  2/14/2008  
Issue and Print Permit  2/14/2008 DONE
Sprinkler Plan Check1/28/2008 2/13/2008 PASS
Details
Note: This was the third review affecting 28 heads. These plans were originally approved in November of 2007. The piping plan was revised to include the addition of 5 heads in the eves. The plan modification also included new water flow information which resulted in a complete recalculation of the system hydraulics. A total of 28 heads were affected by the modification. Of those 28 heads, 23 were existing and 5 others added to the calculated area reviewed. Plans are approved by Bryan Johnson
Plan resubmittals received  1/28/2008  
received "2" fire spr apps, "3" fire submittal booklets, & "3" sets of plans -- plans put on fire shelf
INSP-Sprinkler Rough-in1/2/20081/2/20081/2/2008PPASS
DetailsTroy Cobbley
The sprinkler piping is ok to cover. However resubmittals are required due to additional heads and piping layouts in both of the remote areas.
Issue and Print Permit  11/30/2007 DONE
Sprinkler Plan Check10/31/2007 11/29/2007  
These plans were denied. The designer failed to include the existing back flow device within the calculations as required.
Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set will be maintained for 5 working days. Per Bryan Johnson
PLANS/APPL TAKEN TO FRONT DESK  11/29/2007 DONE
Inspection Record Card- Fire11/29/2007 11/29/2007 DONE
Telephone call  11/29/2007  
tlk to chavez ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  11/29/2007  
Sprinkler Plan Check11/14/2007 11/26/2007 PASS
Plans are approved by Bryan Johnson
Case Summary  11/14/2007 DONE
Plan resubmittals received  11/14/2007  
Received application, and five copies of booklet of submittal info and pages FP1, FP2; taken to fire review
Application received  10/31/2007  
Case Summary  10/31/2007 DONE
Pending Assignment by SAM10/31/2007