Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR07-00905
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 3236 E AMITY RD
Project NameUNG-SPR-MAACO
Customer Number 
ePlanReview 
Description
To install 376 LF of 8 inch C-900 underground automatic fire sprinkler supply piping for future building. Piping will be capped off until future building is constructed. Underground piping shall be flushed and hydro tested per NFPA 13 prior to capping.(*5/20/08 - Plan Modification - To add PIV to underground fire sprinkler supply and contiue approximatley 6 feet of 6 inch C-900 into new building for future overhead fire sprinkler system.)*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/25/20088/25/20088/25/2008APASS
DetailsForrest France
Verified corrections, seismic clearance provided, fire supply line flush completed, UG permit finaled.
INSP-Supply line flush8/22/20088/25/20088/25/2008APART
DetailsForrest France
UG fire supply line flush completed okay.
Override - Parcel Holds8/25/20081/1/19008/25/2008  
final fire
Override - Parcel Holds  8/25/2008  
INSP-Supply line flush8/19/20088/19/20088/20/2008PCANC
DetailsTroy Cobbley
Per Roy a flush will not be performed until the parking lot pavement is done.
Override - Parcel Holds8/19/20081/1/19008/19/2008  
this is for a fire inspection
INSP-Final Inspection6/12/20086/12/20086/12/2008APART
DetailsForrest France
Permit final pending supply line flush.
INSP-Sprinkler Rough-in/Hydro5/27/20085/27/20085/27/2008PPART
DetailsForrest France
UG fire supply line hydrostatic testing for the new portion of installed pipe and ductile riser completed acceptable.
INSP-Sprinkler Rough-in/Hydro5/21/20085/21/20085/21/2008PCANC
DetailsForrest France
Duplicate inspection request already completed.
INSP-Sprinkler Rough-in/Hydro5/20/20085/21/20085/21/2008APART
DetailsForrest France
Additional gate valve, new stub-in and ductile riser are approved for cover, need to plug the open cap at the riser and provide method for seismic clearance where the piping will pass through the floor slab, hydro and flushing not yet completed for this portion of work.
Sprinkler Plan Check5/20/2008 5/20/2008 PASS
DetailsScott Arellano
Plan modification recieved.
PLANS/APPL TAKEN TO FRONT DESK  5/20/2008 DONE
Inspection Record Card- Fire5/20/2008 5/20/2008 DONE
DetailsCathy Brown
Telephone call  5/20/2008 DONE
lft ms for brook ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  5/20/2008 DONE
DetailsCathy Brown
CHANGE STATUS TO (ISS)  5/20/2008 DONE
already issued previously
Plan resubmittals received  5/16/2008 DONE
Plan modification recieved
Plan assigned to (Scott)5/16/2008 5/16/2008 DONE
DetailsCathy Brown
INSP-Supply line flush5/14/20085/15/20085/15/2008AFAIL
DetailsTroy Cobbley
The inspection today was for additional piping, a PIV vavle and the building stub-in. This work is not part of this permits scope of work. A separate permit is required. I contacted John at Commercial Fire about it.
INSP-Sprinkler Rough-in/Hydro4/18/20084/18/20084/18/2008PPART
DetailsForrest France
Final pending supply line flush completion and future building construction for floor slab seisimic clearance.
INSP-Sprinkler Rough-in/Hydro11/21/200711/27/200711/27/2007PPASS
DetailsForrest France
Underground hydro passed..will be capped off until future building is built..As per KR
INSP-Sprinkler Rough-in/Hydro11/21/200711/27/200711/21/2007ACANC
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick
INSP-Final Inspection11/9/200711/13/200711/13/2007APART
DetailsForrest France
Under ground piping is ok to cover.
INSP-Sprinkler Rough-in/Hydro11/9/200711/9/200711/11/2007PFAIL
DetailsForrest France
Ok to cover under ground from the north west corner of the existing building to the future building. NOT OK TO COVER FROM NORTH WEST CORNER OF EXISTING BUILDING TO WATER MAIN, LESS THAN 4' 6" DEEP REQUIRED CODE IS 4' 6".MANY AREAS WERE 3" to 6" TO SHALLOW. DO NOT COVER UNTIL FIELD INSPECTED.
INSP-Sprinkler Rough-in11/8/200711/8/200711/8/2007PFAIL
DetailsForrest France
Plans and permit documents for the UG work could not be located on site at the time of inspection, also noted depth of bury at some locations does not meet min. 4'6" (2"-6" shallow).
Issue and Print Permit  11/6/2007 DONE
Telephone call  11/5/2007 DONE
t/c w brook at ###-#### - permit ready and fees given
Permit Ready to Issue  11/5/2007 DONE
Application received  11/2/2007  
PLANS/APPL TAKEN TO FRONT DESK  11/2/2007 DONE
Sprinkler Plan Check11/2/2007 11/2/2007 PASS
Inspection Record Card- Fire11/2/2007 11/2/2007 DONE
Pending Assignment by SAM11/2/2007