INSP-Final Inspection | 1/12/2008 | 1/14/2008 | 1/14/2008 | A | PASS |
Forrest France
|
|
|
Necessary corrections have been completed, fire sprinkler permit finaled.
|
INSP-Final Inspection | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | FAIL |
Forrest France
|
|
|
Blocked head at the storage room in the basement, need to replace one painted head at the sales floor, mixed temp heads at the west stairway next to the FACP.
|
INSP-Final Inspection | 1/10/2008 | 1/10/2008 | 1/10/2008 | A | FAIL |
Forrest France
|
|
|
Rear exit canopy / roof exceeds the 4 foot width requirements. Need to sprinkler. KR
|
INSP-Final Inspection | 1/8/2008 | 1/9/2008 | 1/9/2008 | A | NR |
Forrest France
|
|
|
Pending related alarm work for system supervision.
|
INSP-Sprinkler Rough-in/Hydro | 12/14/2007 | 12/14/2007 | 12/14/2007 | A | FAIL |
Forrest France
|
|
|
Inspection for cover denied where the two 4" mains pass through the floor without provision for seismic clearance-need to install flex couplings or provide req. clearance per NFPA 13. The three heads at the storefront hard lid ceilings are okay to cover.
|
INSP-Sprinkler Rough-in/Hydro | 12/12/2007 | 12/12/2007 | 12/12/2007 | P | PART |
Forrest France
|
|
|
Over head hydro 1st floor passed.See approved set of plans for areas OK to cover. KR
|
INSP-Sprinkler Rough-in/Hydro | 11/30/2007 | 11/30/2007 | 11/30/2007 | P | PART |
Forrest France
|
|
|
Red lined areas on the plan at the basement level okayed for ceiling cover.
|
Issue and Print Permit | | | 11/28/2007 | | DONE |
|
|
|
|
(F) Reprint permit | | | 11/28/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/27/2007 | | |
|
|
|
|
Telephone call | | | 11/27/2007 | | DONE |
|
|
|
tlk to tom dutkus that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 11/27/2007 | | |
|
|
|
|
Inspection Record Card- Fire | 11/27/2007 | | 11/27/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/5/2007 | | 11/26/2007 | | PASS |
|
|
|
Plans are approved as submitted by Bryan Johnson
|
Application received | | | 11/5/2007 | | |
|
|
|
|
Pending Assignment by SAM | 11/5/2007 | | | | |
|
|
|
|