Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR07-00916
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 4724 W STATE ST
Project NameCOLLISTER SHOPPING CNTR
Customer Number 
ePlanReview 
Description
This fire alarm permit is to relocate the existing building FACP, install non required audible visual notification, provide HVAC monitoring at the FACP of two duct smoke detectors and install a remote annunciator. The fire alarm system includes sprinkler water flow, valve tamper switches, PIV, kitchen hood and manual pull station the 2007 NFPA 72 was used so smoke detection above the FACP is not required. Building permit BLD07-01555 is a remodel, changing occupancy from a former retail space to a new 12,169 sq. ft. assembly library tenant with associated office and storage per approved plans and DRH07-00262. This building is a one-hour rated building. (Type V-A Construction) Work to include some interior demolition work, removing portions of the existing front CMU exterior wall, some new structural steel work for new exterior window and door openings at front exterior wall, new interior walls and doors, new interior finish, new restrooms, fire sprinkler and alarm work, mechanical work including some new units, plumbing work, and electrical work. Special Inspection is required for structural steel work/welding and for epoxy/adhesive anchor installations. The west wall of this tenant space is an existing 2-hour rated fire wall with a 30" minimum parapet. Nonseparated Uses per IBC Section 302.3.1. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building is fully fire sprinklered for area increase. JCB.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/29/2008 DONE
Plans taken to records to scan
INSP-Final Inspection1/23/20081/24/20081/24/2008PPASS
DetailsTroy Cobbley
All corrections were made per Troys notes.KR
INSP-Final Inspection1/22/20081/22/20081/22/2008PFAIL
DetailsTroy Cobbley
The ceiling mounted strobes in the open areas are blocked by duct work and will need to be located where they are visable. All of the wall mounted strobes are mounted too low to meet code requirements. Atleast three of the duct smoke detectors will require manometer testing to verify location. The alarm tech stated that both of the phone lines were disabled. No test was performed.
Inspection Record Card- Fire11/14/2007 11/14/2007 DONE
Telephone call  11/14/2007 DONE
t/c w ken webster at ###-#### - permit ready and fees given
Permit Ready to Issue  11/14/2007 DONE
Issue and Print Permit  11/14/2007 DONE
Plan assigned to (Mike)11/7/2007 11/13/2007 PASS
11/13/2007 16:36:19 MWT - activity updated through activity FIRA22 from case FIR07-00916.
Alarm Plan Check11/13/2007 11/13/2007 PASS
Fire Alarm Review 1st
PLANS/APPL TAKEN TO FRONT DESK  11/13/2007  
Ready for Issue
Application received  11/7/2007