Permit Information
Permit NumberFIR07-00929
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 11345 W EXECUTIVE DR
Project Name 
Customer Number 
ePlanReview 
Description
Scope of Work: Revised 3/28/2008 - There is an upgrade agreement on file, established under BLD05-00127, for installation of a fire suppression (sprinkler) system in the areas immediately behind the main office, labeled on the upgrade agreement plan as 'Warehouse #1' and 'North Loading Dock'. This sprinkler permit (FIR07-00929) is being issued for this required sprinkler work. The 'Office' area is not required to be sprinklered. The associated building permit BLD07-01957 (as modified 3/3/2008) includes the construction of a 135 sq. ft. room in the northwest corner of the existing warehouse for use as a fire sprinkler riser room. (Underground) A new 8" C-900 underground service will be run out 120'-0" from the property line at the North West corner of the Warehouse #1 structure. The underground will be controlled from a new post-indicating valve. The FDC will also be remote of the building, per plans. (Overhead) Two dry pipe & valve / risers will serve through out the warehouse and loading dock. A 1.5" hose valve system will also be installed in the warehouse.
The fire sprinkler system work shall comply with the IFC 2003 and the attached review comments. The approved plans, review comments, permit and fire "Inspection Card" are required to be on site. This permit is attached to building permit: BLD07-01957. ****3/28/2008 Per Sam Rogers, a1,000 sq ft remote area was required to be calculated using a 0.40 density, to prove the system is adequate for an EH2 occupancy for Group A plastics, consisting of couches in wooden crates to be stored along the north & east exterior walls up to 7'-6" high. The total area of couch storage amounts to just under 1,000 sf, which is less than 10% of building space and is therefore treated as Miscellaneous Storage. NO RACK STORAGE IS ALLOWED UNDER THIS PERMIT. SLR
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/2/20085/5/20085/5/2008APASS
DetailsTroy Cobbley
Permit finaled. Storage has been removed from the top of the couch storage bins.
INSP-Final Inspection5/1/20085/2/20085/2/2008AFAIL
DetailsTroy Cobbley
Need the pallets that have been placed on top of the couch storage boxes removed. I let the warehouse manager know that no items can be stored there. The PIV tamper switch needs adjusted so that it reports correctly. The forward flush passed. The trip tests of the two dry systems passed.
INSP-Final Inspection4/8/20084/11/20084/11/2008ACANC
DetailsTroy Cobbley
Per todd the inspection is to be canceled due to the fire alarm system not being ready.
INSP-Sprinkler Rough-in/Hydro4/2/20084/3/20084/3/2008APASS
DetailsTroy Cobbley
24 hour air test passed
INSP-Sprinkler Rough-in4/1/20084/2/20084/2/2008APASS
DetailsTroy Cobbley
24hr Air Test started at 8:30 the left system has 45 psi and the right system has 44 psi.
Issue and Print Permit  4/1/2008  
INSP-Sprinkler Rough-in/Hydro3/28/20083/31/20083/31/2008APASS
DetailsTroy Cobbley
OH Hydro Inspecion passed
Plan resubmittals received  3/31/2008  
Plan assigned to (SAM)3/31/2008 3/31/2008 PASS
DetailsSam Rogers
3/31/2008 13:36:25 SLR - activity updated through activity FIRA22 from case FIR07-00929.
Sprinkler Plan Check3/31/2008 3/31/2008 PASS
DetailsTroy Cobbley
Modified plans reviewed by T. Coobley. New calc's acceptable. Plan annotations have been revised to stipulate the design commodities includes Plastics (couches) in wood crates less than 8' in height, not exceeding 1,000 sf; which is less than 10% of building, therefore classified as Miscellaneous Storage. Resubmitted hydraulic calculations based on the currently issued plans, verify the required EH2 density of 0.40gpm/sf/ over 1,000sf (the max. area of storage) is available without a fire pump. Therefore the currently issued sprinkler layout with no fire pump, based on Class IV piled commodities, with NO RACK STORAGE, is also acceptable for limited storage (not exceeding 1,000 sf) of Plastic commodity (couches in wooden crates) stored less than 8' in height. SLR
PLANS/APPL TAKEN TO FRONT DESK  3/31/2008 DONE
Inspection Record Card- Fire3/31/2008 3/31/2008 DONE
DetailsCathy Brown
Telephone call  3/31/2008 DONE
flt ms with receptionist for geradl ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  3/31/2008 DONE
INSP-Sprinkler Rough-in3/26/20083/28/20083/28/2008APART
DetailsTroy Cobbley
The overhead rough-in as far as piping installation is passed. The wrong heads have been installed. The correct sprinkler heads need to be installed or approval from the plan reviewer is required if they are to be left. The hose valves/piping as shown on the city approved plans has been removed as per Dave Hanniman.
INSP-Sprinkler Rough-in3/26/20083/27/20083/27/2008APASS
DetailsTroy Cobbley
Underground flush passed
Telephone call  3/27/2008 DONE
Telcon today with Randy Bowran, DeBest Fire Protection, ###-####, in follow up to our 3/23/08 telcon. Randy indicated the commodities include couches covered with a plastic bag, two-high, within in wooden 5-sided crates, (i.e. open on one side), with no plastic wrap or encapsulation around the wooden crate. I indicated that commodity falls under the "Plastic" commodity classification, per NFPA 13, TABLE A.5.6.4.1 ("Furniture-wood-with foam plastic cushioning"", not under the Class IV commodity class specified in their design criteria. Randy indicated the owner has agreed to remove all existing racks, and to store all couches in crates as described, along the north and east exterior walls, one crate high (7feet, each crate has an interior shelf so two couched are stored in each crate), and the total floor area occupied would be somewhat less than 1,000 sf. That arrangement would allow this Plastic storage to be considered as Miscellaneous storage, subject to NFPA 13, Chapter 13,;and Table 13.2.1 requires EH2 density of 0.40 gpm/sf/2500 sf. not considering the dry system adjustment. Randy agreed to recalculate the sprinkler system hydraulic performance over the specific floor area of the proposed couch storage to determine what density the system can provide. Randy will advise us of the calculation results and we will then decide whether the protection will be adequate as designed or if other protection measures will be required.
The permit shall not be "finaled" until this issue has been satisfactorily resolved.
INSP-Sprinkler Rough-in/Hydro3/25/20083/25/20083/26/2008PPASS
DetailsTroy Cobbley
UG Hydro Inspection passed for the underground supply and the remote fdc
Telephone call  3/23/2008 DONE
Per the fire alarm plans, there is no fire pump or pump room. I called Randy at DeBest (###-####) and learned that the design for the sprinkler FIR07-00929 permit is based on eliminating the fire pump (which was shown on FIR07-00374) at the request of the owner who told them he would eliminate rack storage and go to solid piled storage. I requested that we visit the site to verify that the owner intends to do that and if he has eliminated the racks yet. We do not want to approve the design/installation of a sprinkler design designed for solid piled storage unless they are willing to first eliminate the existing rack storage. He will set up an appointment for us to visit. Meantime, we are holding off on the approval of the fire alarm permit FIR08-00122.
INSP-Sprinkler Rough-in3/12/20083/13/20083/13/2008PPASS
DetailsTroy Cobbley
The remote FDC piping can be covered.
INSP-Sprinkler Rough-in3/11/20083/13/20083/12/2008ACANC
DetailsTroy Cobbley
UG Cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in3/10/20083/11/20083/11/2008PPASS
DetailsTroy Cobbley
Underground supply piping can be buried. Still need an inspection on the remote FDC piping. I suggested putting in the conduit for the PIV tamper as well prior to bury.
FIR-Aging Inspection3/5/20083/5/20083/7/2008 NR
DetailsTroy Cobbley
WIP
Telephone call  2/5/2008 DONE
Per telcon with Gerald Eberly, this permit was intended to replace and supercede previously issued permit FIR07-00374. I requested he call the permit desk and request FIR07-00374 to be voided.
Inspection Record Card- Fire12/4/2007 12/4/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/4/2007  
Telephone call  12/4/2007 DONE
tlk to gerald ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  12/4/2007 DONE
Issue and Print Permit  12/4/2007 DONE
Sprinkler Plan Check11/13/2007 11/30/2007 PASS
Fire Sprinklers Permit Plan Review done by Bryan Johnson
Application received  11/13/2007  
Pending Assignment by SAM11/13/2007    
Inspection Record Card- Fire3/31/2008