Permit Information
Permit NumberFIR07-00935
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 251 W GOWEN RD
Project NameWestern Trailers
Customer Number 
ePlanReview 
Description
Revised Scope of Work:
The contractor made revisions in the field during construction that resulted in complete resubmittal of the calculations and piping plan. The revisions included pipe size changes and adjustments to the hydraulic and seismic calculations. The revision is dated 06/27/08 and noted to be Rev 1. The original plans were approved with conditions on 12/07/07. During the second review, all of the original conditions of approval were verified for compliance. Scope of Work:
To install a complete wet pipe system in a new 55,415-ft/2, two story building designed for parts storage. This building is fully fire sprinklered. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground supply was permitted separately under FIR07-00812. Both this and the underground permits are attached to building permit: BLD07-01884.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/14/20087/15/20087/15/2008APASS
DetailsForrest France
Chain and lock was added to PIV. New set of resubmitted plans were on site with all corrections made. KR
Telephone call  7/14/2008 DONE
DetailsSam Rogers
Spoke with Bryan Johnson this morning. Plans have been approved and will be available for pick by applicant this afternooon.
PLANS/APPL TAKEN TO FRONT DESK  7/14/2008 DONE
DetailsCathy Brown
Inspection Record Card- Fire7/14/2008 7/14/2008 DONE
DetailsCathy Brown
(F) Reprint permit  7/14/2008 DONE
CHANGE STATUS TO (ISS)  7/14/2008 DONE
DetailsBarbara Stitt
Sprinkler Plan Check7/1/2008 7/11/2008 PASS
Details
As-Built Plans & Calculations are approved By Bryan Johnson
Telephone call  7/11/2008 DONE
Herb, the GC, called inquiring about the progress of the fire sprinkler plan review. Informed Herb that the fire sprinkler plan reviewer has the fire sprinkler plans in his posession and the only case notes state that the "plans are on hold unitl further information recieved". Recommended he contact the sprinkler designer and/or permit applicant, American Fire Protection, to recieve further information regarding the delay of sprinkler plan approval.
Telephone call  7/11/2008 DONE
DetailsSam Rogers
Received call from Jim Daines (American Fire Protection) regarding his concern about the length of time of the resubmitted fire sprinkler plan review. Informed Jim of the most recent case notes regarding "request for more information." Jim has been unsuccessful in his attempts to contact Johnson consulting for further information.
INSP-Final Inspection7/9/20087/10/20087/10/2008AFAIL
DetailsForrest France
Plans are still under review for resubmittals.Fire sprinkler Inspection completed. One remaining item.Chain and lock is required on PIV. KR
Sprinkler Plan Check7/1/2008 7/10/2008 NR
Details
These plans are on hold until further information is known.
Western Trailer FIR07-00935
Approved with Conditions 12/07/2007
Noted Conditions of Approval:

1. Provide an exterior control valve as required. An exterior indicating control valve is required for the fire sprinkler system in this building and provided with valve identification signage. (BMC 7-01-53 IFC 903.1.3) To be field verified. (Field verified by Inspector France but not reflected on the As-Builts)

2. The truck wash bay piping and material shall be corrosion resistant. Where corrosive conditions exist or piping is exposed to the weather, corrosion-resistant types of pipe, fittings, and hangers or protective corrosion-resistant coatings shall be used. (NFPA 13-7.7.5, 8.15.3.2.1*) To be field verified. (Not Verified or reflected on As-Builts)

3. Prior to final approval, an approved rack layout shall be verified to include 19’-0” maximum storage height in the parts warehouse in a single or double row rack configuration with 8’-0” aisles. (Rack Plans were submitted under a separate BLD permit and verified by inspector France. Racks were reflected on the As-Builts as an outline only)

(Recent plan review comments noted in red)

Override - Parcel Holds  7/9/2008  
Override - Parcel Holds  7/9/2008  
Plan resubmittals received  7/1/2008  
DetailsSam Rogers
Pending Assignment by SAM7/1/2008 7/1/2008 DONE
DetailsSam Rogers
INSP-Sprinkler Rough-in/Hydro6/20/20086/20/20086/20/2008PPART
DetailsForrest France
Verified some items per the C/N are finished including added heads at the wash bay, added seismic brace, spacing at the compressor room. Noted fire alarm work is nearly complete including tamper and flow switch wiring and FACP installation prior to the issuance of a fire alarm permit. Double permit fees will apply.
INSP-Sprinkler Rough-in/Hydro6/12/20086/12/20086/12/2008PPART
DetailsForrest France
OH hydrostatic testing for both wet systems passed. OH rough-in failed due to overspaced heads at the wash bay, blocked heads at the compressor room, missing EQ brace at the 4" main NE corner of the warehouse, need to provide resubmittals for pipe size changes at the north office areas, some finish items at the riser are not complete including flex. couplings, FDC ball drip, head box, tagged DCVA, etc.
INSP-Sprinkler Rough-in5/30/20086/3/20086/3/2008PPART
DetailsForrest France
1st and 2nd floor south offices OH rough-in is approved for cover with the exception of one missing EQ brace at the 2nd floor 3" main east side last piece.
Override - Parcel Holds  5/30/2008  
INSP-Sprinkler Rough-in4/11/20084/14/20084/14/2008APASS
DetailsTroy Cobbley
The restroom, shower & locker room area are ok to cover. See the city approved plans for locations.
INSP-Sprinkler Rough-in/Hydro3/25/20083/25/20083/25/2008PNR
DetailsForrest France
Not completed for inspection.
FIR-Aging Inspection3/20/20083/20/20083/20/2008 DEFR
DetailsForrest France
Work in progress, construction underway.
Issue permit  12/14/2007  
PLANS/APPL TAKEN TO FRONT DESK  12/11/2007 DONE
Inspection Record Card- Fire12/11/2007 12/11/2007 DONE
Telephone call  12/11/2007  
lft vm for jim danes ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  12/11/2007 DONE
lft vm for jim danes ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  12/11/2007 DONE
Sprinkler Plan Check11/15/2007 12/7/2007 PASS
Plans are approved w/conditions by Bryan Johnson
Case Summary  11/15/2007 DONE
Application received  11/15/2007  
Pending Assignment by SAM11/15/2007