Permit Information
Permit NumberFIR07-00937
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 2580 W WILLIAMSPORT LN
Project NameVISTA FOURPLEX
Customer Number 
ePlanReview 
Description
Scope of Work: To install a fire life safety NFPA 13R system to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape or be evacuated, in a new 5,556-ft/2 three story, four unit apartment building starting at the top of a 2” Ames Series 007 Backflow Double Check control. System shall be equipped with an alarm initiating device connected to an alarm system and an outside annunciating devise. All fire sprinkler work and related, which includes a dedicated service underground water supply, the system backflow prevention device, shall be per NFPA 13R, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-02528. Revised Scope of Work: These previously approved plans and calculations were resubmitted due to changes made during construction that affected the remote area of operation. The modifications include adding 4 pendants, two on each level to meet code compliance. The two dry HSW heads second floor serving the decks were relocated. In addition, a second feed main to the second floor from the first was added. Design area 1 was affected. These modifications of the plans as they were approved do not appear to adversely affect the systems operation. The revisions are noted as 1 -6 and dated 03-04-08.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/18/20083/19/20083/19/2008APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection3/17/20083/18/20083/18/2008AFAIL
DetailsForrest France
Provide service tag at the riser, provide "911" sign at the outside bell, missing escutcheons at some locations, one blocked head at a kitchen area by an adjacent light fixture.
INSP-Sprinkler Rough-in/Hydro3/17/20083/17/20083/17/2008PPART
DetailsForrest France
UG fire supply line hydrostatic test completed satisfactory.
INSP-Supply line flush3/17/20083/17/20083/17/2008PPART
DetailsForrest France
UG fire supply line flush completed in conjunction with United Water company.
CHANGE STATUS TO (ISS)  3/17/2008  
already issued previously-- gave plans to customer
Inspection Record Card- Fire3/14/2008 3/14/2008 DONE
DetailsPatricia Smith
Telephone call  3/14/2008 DONE
t/c w brook nelson at ###-#### - permit ready and no fee
Permit Ready to Issue  3/14/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  3/14/2008 DONE
Sprinkler Plan Check3/4/2008 3/12/2008 PASS
Details
as-built plans and calculations approved
Plan resubmittals received  3/4/2008  
Plan modification: received three copies of application, hydraulic calculations, product info, and four copies of sheets FP-1, FP-2; routed to fire review
INSP-Sprinkler Rough-in2/20/20082/21/20082/21/2008ACANC
DetailsForrest France
Per bruce.
INSP-Sprinkler Rough-in/Hydro12/24/200712/26/200712/26/2007APART
DetailsForrest France
Verified tenting installation at the third floor. OH fire sprinkler piping is okay for cover pending satisfactory plan resubmittals reflecting field modifications in piping layout including main/branch lines and changed head locations.
INSP-Sprinkler Rough-in12/24/200712/24/200712/24/2007PPART
DetailsForrest France
OH hydrostatic retest completed and passed per inspection done 12/21. No access provided to perform inspection for cover at the third floor today, noted insulation at the third floor does not appear to be finished at this time.
INSP-Sprinkler Rough-in/Hydro12/18/200712/19/200712/19/2007AFAIL
DetailsForrest France
OH Hydrostatic test failed due to 25 psi. pressure loss at the guage.
INSP-Sprinkler Rough-in12/17/200712/17/200712/18/2007PNR
DetailsForrest France
bruce - please call 1/2 hr prior to inspection Phone #: ###-####
INSP-Sprinkler Rough-in12/13/200712/14/200712/14/2007AFAIL
DetailsForrest France
Noted significant changes regarding the actual installation v. approved plans (main and branchline changes, supply riser changes, added heads, relocated sw heads, etc.), noted missing heads at closets on the 2nd floor, missing heads under the stairs 1st floor, added heads in mech, closets, branchline changes at the design area, noted the UG supply has been installed and covered without an inspection and will not be accepted until conditions of approval are met.
INSP-Sprinkler Rough-in12/13/200712/13/200712/13/2007PCANC
DetailsForrest France
Inspection to be rescheduled as discussed, noted contractor has been issued the permit and called for a system rough-in inspection the same day.
PLANS/APPL TAKEN TO FRONT DESK  12/13/2007 DONE
Inspection Record Card- Fire12/13/2007 12/13/2007 DONE
Telephone call  12/13/2007 DONE
lft ms with receptionist for brooks ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  12/13/2007 DONE
Issue and Print Permit  12/13/2007 DONE
Sprinkler Plan Check11/19/2007 12/10/2007 PASS
These plans were approved per attached comments with conditions by Bryan Johnson
Application received  11/19/2007  
Pending Assignment by SAM11/19/2007