INSP-Final Inspection | 4/21/2008 | 4/22/2008 | 4/22/2008 | A | PASS |
Forrest France
|
|
|
Noted defficient items verified for completion, fire sprinkler permit work passed final inspection, permit finaled.
|
INSP-Final Inspection | 4/18/2008 | 4/21/2008 | 4/21/2008 | A | FAIL |
Forrest France
|
|
|
Pendent head deflector at a storage closet is cut above the drop ceiling and missing escutcheon, noted the need to maintain 18" clearance to storage below sprinkler heads at the kitchen areas.
|
INSP-Sprinkler Rough-in | 4/11/2008 | 4/14/2008 | 4/14/2008 | A | PART |
Forrest France
|
|
|
Noted defficient items from the previous inspection are corrected, OH rough-in at the drop ceilings throughout tenant improvement are approved for cover, one mechanical closet at the east side is missing coverage-to be added and verified at final inspection-see plans for location.
|
INSP-Sprinkler Rough-in | 3/26/2008 | 3/27/2008 | 3/27/2008 | A | FAIL |
Forrest France
|
|
|
Red-lined areas on stamped plan set in need of revision prior to approval for cover including blocked or overspaced upright heads at various locations and missing coverage at a storage room. Not all areas ready for inspection at this time, see plans for annotations.
|
FIR-Aging Inspection | 3/21/2008 | 3/21/2008 | 3/21/2008 | | DONE |
Forrest France
|
|
|
Work in progress, construction underway. Activity pending site inspection request.
|
Issue permit | | | 12/20/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/18/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/18/2007 | | 12/18/2007 | | DONE |
|
|
|
|
Telephone call | | | 12/18/2007 | | DONE |
|
|
|
tlk to greg johnson ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 12/18/2007 | | |
|
|
|
|
Sprinkler Plan Check | 11/27/2007 | | 12/17/2007 | | PASS |
|
|
|
Plans approved as submitted by Bryan Johnson
|
Case Summary | | | 11/27/2007 | | |
|
|
|
|
Application received | | | 11/27/2007 | | |
|
|
|
|
Pending Assignment by SAM | 11/27/2007 | | | | |
|
|
|
|