Miscellaneous action | | | 7/17/2009 | | DONE |
|
|
|
Taken to records for scanning.
|
INSP-Final Inspection | 6/29/2009 | 6/30/2009 | 6/30/2009 | P | PASS |
Forrest France
|
|
|
Correction notice items verified for completion, final site fire alarm testing passed, permit finaled.
|
INSP-Final Inspection | 6/18/2009 | 6/19/2009 | 6/22/2009 | P | PART |
Forrest France
|
|
|
See inspection comments 6/22.
|
INSP-Final Inspection | 6/19/2009 | 6/22/2009 | 6/22/2009 | P | PART |
Forrest France
|
|
|
Items needed for final include adjustment at the PIV tamper switch, program door holds at two locations to release on general alarm conditon, elevator recall functions did not operate correctly. Remainder of installation passed field testing.
|
INSP-Final Inspection | 6/17/2009 | 6/17/2009 | 6/17/2009 | P | PART |
Forrest France
|
|
|
Missing current set of approved plans on site for inspection as requested.
|
INSP-Final Inspection | 6/15/2009 | 6/16/2009 | 6/16/2009 | P | CANC |
Forrest France
|
|
|
ryan - after 2 please Phone #: ###-#### Rescheduled per conversation with contractor.
|
INSP-Final Inspection | 6/11/2009 | 6/12/2009 | 6/12/2009 | P | CANC |
Troy Cobbley
|
|
|
Cancelled per Forrest. To be rescheduled for next week.
|
CHANGE STATUS TO (ISS) | | | 6/3/2009 | | DONE |
|
|
|
|
(F) Reprint permit | | | 6/3/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Permit Ready to Issue | | | 6/2/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/2/2009 | | 6/2/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 6/2/2009 | | DONE |
|
|
|
Left message that permit is ready for pick up///6-2-09 @ 8:05am BAS
|
Plan assigned to (Stephanie) | 5/28/2009 | | 6/1/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
6/1/2009 15:52:11 SLC - activity updated through activity FIRA24 from case FIR07-00971.
|
Alarm Plan Check | 6/1/2009 | | 6/1/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 6/1/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Plan resubmittals received | | | 5/28/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
Plan Mod rec'd- one copy of app and submittal info
|
INSP-Alarm Testing | 5/8/2009 | 5/11/2009 | 5/13/2009 | P | FAIL |
Forrest France
|
|
|
Need to provide NFPA 72 record of inspection and testing including a signals list prior to final on site acceptance test, missing building map at the FACP for device and zone locations, field installation does not match approved plans including sprinkler risers, deleted/added devices, etc., plan resubmittals are necessary to reflect changes, noted some minor field adjustments to be made for spacing of notification devices.
|
INSP-Alarm Testing | 5/6/2009 | 5/7/2009 | 5/7/2009 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 5/6/2009 at 12:19:58 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 7 2009 10:32AM.
|
INSP-Alarm Testing | 4/27/2009 | 4/30/2009 | 4/29/2009 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 4/27/2009 at 4:00:14 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Apr 29 2009 1:32PM.
|
INSP-Alarm Testing | 4/23/2009 | 4/27/2009 | 4/27/2009 | P | NR |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 4/23/2009 at 10:21:08 AM. Contact: ###-####. Contractor not available for site inspection per phone conversation.
|
INSP-Final Inspection | 2/18/2009 | 2/19/2009 | 2/19/2009 | A | DEFR |
Forrest France
|
|
|
Casey- call 30 mins prior to going Phone #: ###-#### * NOTE * Wrong permit number requested by contractor-Intended for project related fire sprinkler work.
|
INSP-Final Inspection | 2/17/2009 | 2/18/2009 | 2/18/2009 | A | CANC |
Forrest France
|
|
|
Jerry- call 30 mins prior to going Phone #: ###-####
|
Telephone call | | | 7/21/2008 | | DONE |
|
|
|
Spoke with John at Fire Sentry who stated one part of the building is close to being completed, however work still continues on the Funston site of the building.
|
Telephone call | | | 7/17/2008 | | DONE |
|
|
|
Left a message asking for the status
|
INSP-Conference | 3/31/2008 | 4/1/2008 | 4/1/2008 | P | CANC |
Forrest France
|
|
|
Wrong permit called in for conference.Will call in correct permit.KR
|
Issue and Print Permit | | | 1/3/2008 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 12/27/2007 | | 12/28/2007 | | PASS |
|
|
|
12/28/2007 13:30:20 MWT - activity updated through activity FIRA22 from case FIR07-00971.
|
Alarm Plan Check | 12/28/2007 | | 12/28/2007 | | PASS |
Michael Timmerman
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/28/2007 | | DONE |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 12/28/2007 | | 12/28/2007 | | DONE |
|
|
|
|
Telephone call | | | 12/28/2007 | | DONE |
|
|
|
lft ms for john lopez ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 12/28/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/27/2007 | | |
|
|
|
received "3" sets of plans & the app
|
Issue and Print Permit | | | 12/6/2007 | | DONE |
|
|
|
issued by mistake
|
Plan assigned to (Mike) | 12/6/2007 | | 12/6/2007 | | DONE |
|
|
|
change status back to review, issued by mistake
|
Miscellaneous action | | | 12/6/2007 | | DONE |
|
|
|
picked up failed plans, resubmittals required
|
Alarm Plan Check | 12/5/2007 | | 12/5/2007 | | FAIL |
Michael Timmerman
|
|
|
Fire Alarm Review 1st
|
Telephone call | | | 12/5/2007 | | DONE |
|
|
|
left message w jimmy for john lopez at ###-#### - permit needs to be picked up and resubmitted
|
Application received | | | 11/30/2007 | | |
|
|
|
|
Case Summary | | | 11/30/2007 | | DONE |
|
|
|
|