INSP-Final Inspection | 1/2/2008 | 1/2/2008 | 1/2/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. Three doors had to be adjusted while I waited and the batteries were replaced due to cracks in the casing.
|
INSP-Final Inspection | 12/26/2007 | 12/27/2007 | 12/27/2007 | A | FAIL |
Troy Cobbley
|
|
|
Forgot to add the two smoke detectors in the offices that were shown on the approved set of plans, will call in permit when ready. KR
|
Issue permit | | | 12/10/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 12/5/2007 | | 12/7/2007 | | PASS |
|
|
|
12/7/2007 15:48:18 MWT - activity updated through activity FIRA22 from case FIR07-00981.
|
Alarm Plan Check | 12/7/2007 | | 12/7/2007 | | PASS |
Michael Timmerman
|
|
|
Fire Alarm Quick Permit "Pass" See Scope of Work. This permit is subject to field inspection and testing. Field verify that door hold opens release on general alarm and AC power fail. These door hold opens are not allowed to be battery backed. Power Supply Battery Amp Hours not large enough to support door hold opens and NAC devices. No Documents Attached
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/7/2007 | | DONE |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 12/7/2007 | | 12/7/2007 | | DONE |
|
|
|
|
Telephone call | | | 12/7/2007 | | DONE |
|
|
|
tlk to mary of alarmco ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 12/7/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/7/2007 | | 12/7/2007 | | DONE |
|
|
|
|
Application received | | | 12/5/2007 | | |
|
|
|
|