Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR07-00981
StatusFinaled
Name ALARMCO
Site Address 10250 W SMOKE RANCH DR
Project NameSEASONS AT BOISE
Customer Number 
ePlanReview 
Description
This fire alarm quick permit is to install two smoke detectors inside two offices on an existing zone and four door hold opens on an existing door hold open circuit. One door hold open will be located at the kitchen door, one at the salon, and two office doors located next to each other. No building permit is associated with this work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/2/20081/2/20081/2/2008PPASS
DetailsTroy Cobbley
Permit finaled. Three doors had to be adjusted while I waited and the batteries were replaced due to cracks in the casing.
INSP-Final Inspection12/26/200712/27/200712/27/2007AFAIL
DetailsTroy Cobbley
Forgot to add the two smoke detectors in the offices that were shown on the approved set of plans, will call in permit when ready. KR
Issue permit  12/10/2007 DONE
Plan assigned to (Mike)12/5/2007 12/7/2007 PASS
12/7/2007 15:48:18 MWT - activity updated through activity FIRA22 from case FIR07-00981.
Alarm Plan Check12/7/2007 12/7/2007 PASS
DetailsMichael Timmerman
Fire Alarm Quick Permit "Pass" See Scope of Work. This permit is subject to field inspection and testing. Field verify that door hold opens release on general alarm and AC power fail. These door hold opens are not allowed to be battery backed. Power Supply Battery Amp Hours not large enough to support door hold opens and NAC devices. No Documents Attached
PLANS/APPL TAKEN TO FRONT DESK  12/7/2007 DONE
Ready for Issue
Inspection Record Card- Fire12/7/2007 12/7/2007 DONE
Telephone call  12/7/2007 DONE
tlk to mary of alarmco ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  12/7/2007 DONE
Inspection Record Card- Fire12/7/2007 12/7/2007 DONE
Application received  12/5/2007