Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR07-00998
StatusFinaled
Name GUARDIAN ALARM SYSTEMS LLC
Site Address 6352 N ROE ST
Project NameThe Cottages of Boise #2
Customer Number 
ePlanReview 
Description
This permit is to install a new fire R4 assisted living center. The building is fully sprinklered and per an agreement to allow an R4 occupancy requires a manual and automatic fire alarm system throughout in all but sleeping areas. Sleeping areas shall be provided with single station smoke detectors. Building permit # BLD05-01602 is to construct a new 9,606 square feet, two story, maximum 16 residence, 14 bedroom, assisted living facility, licensed by the State of Idaho, Facility Standards. NOTE: Per signed and approved alternate letter dated 1/20/06, a maximum of 5 people will be permitted to reside in this facility which will require assistance from the staff to evacuate the building in an emergency situation and there shall always be at least one employee of the owner in this building at all times. The following items are required throughout. The installation of a NFPA 13 fire sprinkler system with quick response heads, a manual and automatic fire alarm system, a fire detection system in all areas other than the patient sleeping rooms, smoke alarms shall be installed in all sleeping rooms, incidental use separation as required by Section 302.1.1.1, an one-hour fire barrier is required between the garage and the residence and a one-hour horizontal fire assembly is required between the first and second floor . The first floor is 8,198 sq.ft with an attached 525 sq.ft. garage. The second floor is 903 sq.ft and is used for staff offices. All construction per the approved plans and attached comment list. MJP CUP04-00100 CAR 04-00036
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  10/20/2008 DONE
INSP-Final Inspection6/10/20086/11/20086/11/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing5/30/20086/2/20086/2/2008PCANC
DetailsTroy Cobbley
Matt; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
Telephone call  3/13/2008 DONE
left message w allie for matt casey at ###-#### - permit ready and fees given
Permit Ready to Issue  3/13/2008 DONE
Issue and Print Permit  3/13/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  3/12/2008  
Inspection Record Card- Fire3/12/2008 3/12/2008 DONE
DetailsPatricia Smith
Plan assigned to (Mike)12/12/2007 2/4/2008 PASS
DetailsCathy Brown
2/4/2008 10:09:09 CMB - activity updated through activity FIRA22 from case FIR08-00015.
Meeting  1/29/2008 DONE
Walk-in meting requested by architect Dave Davies to discuss a request for approval to install mag locks on three 80" exit doors, which would obstruct the opening height by 3 inches; no alternative was proposed for obstructing the required opening height. I indicated that would not be an acceptable obstruction and he agreed to use another model which mounts of the exterior and does not obstruct the existing 80" clear opening. We reviewed IBC 1008.1.8.6 I requirements. I also advised him to promptly advise the FA Engineer, who is about to approve the alarm shop drawings. Ihe PE will need to modify his FA design, resubmit it to the FA vendor who will change the shop drawings, then route them back to the PE for approval and then resubmit them to us, before we issue the fire alarm plans. Dave agreed to do so.
Telephone call  1/7/2008 DONE
Called Guardian Alarms - left Msg that I need notification appliance circuit current totals, how they were derived. Don't match with what data sheets say.
Miscellaneous action  1/7/2008 DONE
Plan review completed holding until engineers review complete.
Alarm Plan Check1/4/2008 1/7/2008 PEND
DetailsMichael Timmerman
Fire Alarm Review 2nd
Telephone call  1/4/2008 DONE
Called Matt Casey Fire Alarm Applicant. Told Matt that we require a letter of review from the design engineer of the shop drawings. I him know we need this letter before I issue the resubmitted plan. (This requirement was stated in the 1st review)
Miscellaneous action  1/4/2008 DONE
Received a phone call from fire alarm vendor checking on status of resubmittals. Permit Fir07-00998 and Fir07-00999 were logged in as the same project. Corrected by Mike Timmerman
Plan resubmittals received  1/3/2008 DONE
received 6 copies of sheets FA1,FA2,FA3,FA4 and 2 applications dent to fire///dld
Alarm Plan Check12/13/2007 12/13/2007 FAIL
DetailsMichael Timmerman
Fire Alarm Review 1st
Miscellaneous action  12/13/2007 DONE
Faxed Copy of Failed Plan Review to Matt Casey ###-#### and Engineer Jon Van Stone ###-####
Telephone call  12/13/2007 DONE
lft vm with matt casey ###-#### that permit has to resubmittal required on both sets
Case Summary  12/12/2007  
Application received  12/12/2007