Case Summary | | | 10/20/2008 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/17/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 6/10/2008 | 6/10/2008 | 6/10/2008 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Alarm Testing | 6/9/2008 | 6/10/2008 | 6/10/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 6/4/2008 | 6/5/2008 | 6/5/2008 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 6/3/2008 | 6/4/2008 | 6/4/2008 | P | FAIL |
Troy Cobbley
|
|
|
Provide an additional smoke detector near the main entrance as discussed and relocate the manual pull station to within 5' of the same door. Provide asbuilts showing the deletion of the NAC panel and new battery calculations.
|
INSP-Alarm Testing | 5/30/2008 | 6/2/2008 | 6/2/2008 | A | CANC |
Troy Cobbley
|
|
|
Matt; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
Telephone call | | | 3/13/2008 | | DONE |
|
|
|
left message w allie for matt casey at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/13/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/13/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/12/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 3/12/2008 | | 3/12/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/7/2008 | | DONE |
|
|
|
telcon from Matt with Gardian re status. Found resubmittal had been placed out of sight and therefore had been overlooked. Will do review on Monday.
|
Plan resubmittals received | | | 2/21/2008 | | |
|
|
|
Additional information recieved from Guardian Alarm///2-21-08 @12:05pm BAS
|
Meeting | | | 1/29/2008 | | DONE |
|
|
|
Walk-in meting requested by architect Dave Davies to discuss a request for approval to install mag locks on three 80" exit doors, which would obstruct the opening height by 3 inches; no alternative was proposed for obstructing the required opening height. I indicated that would not be an acceptable obstruction and he agreed to use another model which mounts of the exterior and does not obstruct the existing 80" clear opening. We reviewed IBC 1008.1.8.6 I requirements. I also advised him to promptly advise the FA Engineer, who is about to approve the alarm shop drawings. Ihe PE will need to modify his FA design, resubmit it to the FA vendor who will change the shop drawings, then route them back to the PE for approval and then resubmit them to us, before we issue the fire alarm plans. Dave agreed to do so.
|
Plan assigned to (Mike) | 12/12/2007 | | 1/28/2008 | | PASS |
Patricia Smith
|
|
|
1/28/2008 11:00:39 P_S - activity updated through activity FIRA22 from case FIR07-01013.
|
Alarm Plan Check | 1/7/2008 | | 1/7/2008 | | PEND |
Michael Timmerman
|
|
|
Fire Alarm Review 2nd
|
Telephone call | | | 1/7/2008 | | DONE |
|
|
|
Called Guardian Alarms - left Msg that I need notification appliance circuit current totals, how they were derived. Don't match with what data sheets say.
|
Miscellaneous action | | | 1/7/2008 | | DONE |
|
|
|
Plan review completed holding until engineers review complete.
|
Telephone call | | | 1/4/2008 | | DONE |
|
|
|
Called Matt Casey Fire Alarm Applicant. Told Matt that we require a letter of review from the design engineer of the shop drawings. I him know we need this letter before I issue the resubmitted plan. (This requirement was stated in the 1st review)
|
Plan resubmittals received | | | 1/3/2008 | | DONE |
|
|
|
Resubmitted plans were received and placed in fire review box. They were not logged in as received. Entry made by Mike Timmerman
|
Alarm Plan Check | 12/13/2007 | | 12/13/2007 | | FAIL |
Michael Timmerman
|
|
|
Fire Alarm Review 1st
|
Miscellaneous action | | | 12/13/2007 | | DONE |
|
|
|
Faxed Copy of Failed Plan Review to Matt Casey ###-#### and Engineer Jon Van Stone ###-####
|
Telephone call | | | 12/13/2007 | | DONE |
|
|
|
lft vm with matt casey ###-#### that permit has to resubmittal required on both sets
|
Case Summary | | | 12/12/2007 | | |
|
|
|
|
Application received | | | 12/12/2007 | | |
|
|
|
|
Alarm Plan Check | 3/12/2008 | | | | PASS |
|
|
|
engineer review completed
|
Alarm Plan Check | 3/12/2008 | | | | PASS |
|
|
|
engineer review completed
|