Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR07-01000
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 928 W MAIN ST
Project NameIDANHA BUILDING
Customer Number 
ePlanReview 
Description
This permit is to tie in a waterflow and tamper switch located in the 6th floor stairwell heading up to the penthouse, and tie in a kitchen hood to the fire alarm system. Alarm vendor indicated that the flows and tampers must have been installed after the building sprinkler system was installed. However, no sprinkler permit was found for the installation of this flow and tamper switch. The flow switch and tamper switch need to me monitored by the building fire alarm system. An MIS permit MIS05-00136 was issued and finaled for the Bombay Grill. This permit includes connecting a kitchen hood in the Bombay Grill to the fire alarm system. Two kitchen hood permits were found FIR06-00029 and FIR06-00593. Neither permit indicates which restaurant or tenant improvement they were for.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/15/20085/20/20085/21/2008PPASS
DetailsForrest France
All six items per letter dated march 28, 2008 to Ken Howell have been resolved.KR
INSP-Conference3/31/20084/2/20084/2/2008PDONE
DetailsForrest France
conferences for the corrections that needed to be addresss per notes from Sam Rogers and Ken Roule.KR
Miscellaneous action  3/31/2008 DONE
Letter sent certified mail to Ken Howell, Parklane, to follow-up on outstanding bond received 2/21/2002 under BLD99-03148 to allow partial occupancy of building, relating to this FA permit and sprinkler permit FIR04-00490. Document attached.
Case Summary  3/11/2008  
INSP-Final Inspection3/5/20083/6/20083/7/2008PFAIL
DetailsForrest France
Site inspection comments per K.Roule
Tested FA monitoring of VT and waterflow (by manual means). Both annunciated correctly at panel and offsite monitoring station. Visually observed location of dry sidewall sprinkler installed in exterior chimney. Work remaining on this permit:
1. Test the new fire alarm monitoring module which was installed on the existing cooking hood suppression system under this permit. (Requires the hood fire suppression system contractor to be present)
2. Test the waterflow alarm switch by flowing water from the test connection. (Requires the sprinkler contractor responsible for FIR04-00490 be present).
3. Provide fire alarm-initiated interlocks which shut off the hood exhaust fan and the gas fuel to the cooking appliances, as specified in the signed Fire Department Agreement dated 2/4/2004 and in F.Varley's letter dated 4 Feb 2002 letter (Item 2).
4. Correct the existing "trouble" condition on the fire alarm panel.
5. Provide an updated alarm map reflecting the current floor plan and all initiating device locations correlated with the annunciated fire alarm device addresses. (NFPA 72 4.4.6.1).
6. Replace the missing door latch on the FACP cabinet and update the outdated monitoring company and account information currently posted inside the cabinet.
Case Summary  3/6/2008  
INSP-Conference1/7/20081/8/20081/8/2008ADONE
DetailsForrest France
On site conference to discuss hood suppression system interconnections to the building fire alarm system and programming for the new sprinkler WF and TS at the exhaust duct DSW.
Plan assigned to (Mike)12/12/2007 12/13/2007 PASS
12/13/2007 08:39:51 MWT - activity updated through activity FIRA22 from case FIR07-01000.
Alarm Plan Check12/13/2007 12/13/2007 PASS
DetailsMichael Timmerman
Fire alarm Quick permit "Pass" This permit is subject to field inspection and testing. No building permit or written documents are attached.

Note If this is a new kitchen hood and if the 6th floor sprinkler waterflow and tamper switch were recently installed, permits must be issued to perfom the hood installation and sprinkler modification before this permit can be finaled.
PLANS/APPL TAKEN TO FRONT DESK  12/13/2007 DONE
Ready for Issue
Inspection Record Card- Fire12/13/2007 12/13/2007 DONE
Telephone call  12/13/2007 DONE
t/c w david at ###-#### - permit ready and fees given
Permit Ready to Issue  12/13/2007 DONE
Issue permit  12/13/2007 DONE
Application received  12/12/2007