Permit Information
Permit NumberFIR07-01022
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 877 W MAIN ST
Project NameWELLS FARGO BUILDING
Customer Number 
ePlanReview 
Description
This fire alarm quick permit is to install heat detectors used for shunt trip purposes in the elevator hoistways, pits and mechanical rooms of the Wells Fargo Building. Heat detectors are required to be installed within 2' of each sprinkler head installed in the elevator equipment rooms and hoistways. No building permit is associated with this work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/27/20088/28/20088/28/2008PPASS
DetailsForrest France
Heat detector in frieght elevator control room was repaired and tested, per last inspection. KR
INSP-Final Inspection8/4/20088/6/20088/6/2008PFAIL
DetailsForrest France
Main elevator heat detectors in shaft, test completed.Heat detectors in main elevator control room, test completed. Heat detector in frieght elevator shaft, test complete. Heat detector in frieght elevator control room failed due to short in wiring need to re-test. Panel in trouble. KR
INSP-Conference3/18/20083/18/20083/18/2008PDONE
DetailsForrest France
Regarding after hours inspection scheduling.
INSP-Conference12/21/200712/24/200712/24/2007ADONE
DetailsForrest France
On site visit regarding heat and SD device locations at the elevator penthouse, hoistway and pit areas.
Issue and Print Permit  12/21/2007 DONE
Plan assigned to (Mike)12/18/2007 12/20/2007 PASS
12/20/2007 15:30:52 MWT - activity updated through activity FIRA22 from case FIR07-01022.
Alarm Plan Check12/20/2007 12/20/2007 PASS
DetailsMichael Timmerman
Fire Alarm Quick Permit "Hold" " PASS" Changes Made answering questions. Waiting for response from Charlie at Simplex ###-####; I have questions on the submitted alarm matrix Elevator Heat Detectors not indicated on how they are to be programmed. Also an elevator machine room and shaft shown without heat detectors "Why". This permit is subject to field inspection and testing. No written documents are attached.
Telephone call  12/20/2007 DONE
Called Simplex Grinnell ###-#### - Left message for Charlie to call me. I have problems with this quick permit, need answers.
PLANS/APPL TAKEN TO FRONT DESK  12/20/2007 DONE
Readu For Issue
Inspection Record Card- Fire12/20/2007 12/20/2007 DONE
Telephone call  12/20/2007 DONE
t/c w ken at ###-#### - permit ready and fees given
Permit Ready to Issue  12/20/2007 DONE
Application received  12/18/2007