DOC - Permit Finaled | | | 8/3/2009 | | DONE |
|
|
|
finaled by tim frost
|
INSP-Sprinkler Rough-in/Hydro | 12/20/2007 | 12/21/2007 | 12/21/2007 | P | PART |
Forrest France
|
|
|
Verified OH hydrostatic test, noted coverage obstruction at one location, need to provide relief valve at the riser due to the grid system design.
|
Application received | | | 12/20/2007 | | |
|
|
|
|
Sprinkler Plan Check | 12/19/2007 | | 12/20/2007 | | PART |
|
|
|
Plans received to install the overhead throught the remaining half of the building but NOT include installation of the underground main and water connection. The overhead system will remain a dry pipe, manual system per approval of the fire chelf, Renn Ross and Fire Marshal Dave Hanneman. The water connection and riser are still expected to be installed in Feb/Mar when grant funds become available, and that work will be done under a Phase 3 permit. Phase 1 and Phase 2 pemits will remain in the PART approved status until the complete system is finaled under Phase 3. These Phase 2 plans are approved for installation, but as with Phase 1, will not be officially "ISSUED", since this is still a partial system installation. @00F heads approved instead of 155 F heads used in Phase 1, due to contractor's concern for higher temp's at roof deck level.
|
Miscellaneous action | | | 12/19/2007 | | DONE |
|
|
|
Early Start Approval granted, based on telcon requrest from Ron Larson, Viking Sprinkler, due to the expedited nature of this work, so as to have the system installed and approved for temporary occuancy prior to Christmas.
|
Pending Assignment by SAM | 12/20/2007 | | | | |
|
|
|
|