Miscellaneous action | | | 4/29/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 3/25/2008 | 3/26/2008 | 3/26/2008 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 3/19/2008 | 3/20/2008 | 3/20/2008 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
INSP-Final Inspection | 3/20/2008 | 3/20/2008 | 3/20/2008 | P | CANC |
Troy Cobbley
|
|
|
Panel is not clear and has a supervisory for a low air do to a compressor that has malfunctioned. Brett Anderson of Mountain Alarm was notified that the issue will have to be resolved before fire alarm permit is finaled.
|
INSP-Final Inspection | 3/14/2008 | 3/19/2008 | 3/19/2008 | A | FAIL |
Troy Cobbley
|
|
|
Panel was not clear and had troubles for knox box monitoring and sprinkler system low air. Did not have an updated fire alarm map. No other testing perfomed. KR
|
INSP-Final Inspection | 3/10/2008 | 3/12/2008 | 3/12/2008 | A | FAIL |
Forrest France
|
|
|
Descriptor for the new manual pull station is not accurate, need to provide an updated map at the panel reflecting correct floorplan and device locations, duct detectors could not be tested due to locked thermostat controls for the HVAC units, lock at the panel breaker installed while on site, one overspaced notification device repositioned while on site, 95cd ceiling mounted appliances not to exceed spacing guidelines, recommend lower decible settings at the restrooms due to sound pressure levels near 110 dBA at the minimum hearing distance, EOL voltage not tested at this time.
|
Inspection Record Card- Fire | 3/4/2008 | | 3/4/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/4/2008 | | DONE |
|
|
|
t/c w bret anderson at ###-#### - permit ready to be picked - no fee
|
Permit Ready to Issue | | | 3/4/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/4/2008 | | |
|
|
|
no fee due changed status to issued
|
Plan assigned to (SAM) | 2/28/2008 | | 3/3/2008 | | PASS |
Kenneth R Roule
|
|
|
No new fire plan review notes.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/3/2008 | | |
|
|
|
|
Plan resubmittals received | | | 2/28/2008 | | |
|
|
|
plan modification accepted; received application and two folders of submittal info and plan sheets F0.0, F1.0, F1.1; taken to fire plan review
|
Issue and Print Permit | | | 1/23/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/28/2007 | | 12/28/2007 | | DONE |
|
|
|
|
Telephone call | | | 12/28/2007 | | DONE |
|
|
|
t/c w bret anderson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 12/28/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 12/26/2007 | | 12/27/2007 | | PASS |
|
|
|
12/27/2007 15:30:41 MWT - activity updated through activity FIRA22 from case FIR07-01043.
|
Alarm Plan Check | 12/27/2007 | | 12/27/2007 | | PASS |
Michael Timmerman
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/27/2007 | | DONE |
|
|
|
Ready for Issue
|
Case Summary | | | 12/26/2007 | | |
|
|
|
|
Application received | | | 12/26/2007 | | |
|
|
|
|