Miscellaneous action | | | 4/29/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 4/3/2008 | 4/4/2008 | 4/4/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm test complete. KR
|
INSP-Final Inspection | 4/3/2008 | 4/3/2008 | 4/3/2008 | P | FAIL |
Forrest France
|
|
|
All duct detector wiring were open air splices with wire nuts and not installed in back boxes. No other testing performed.KR
|
INSP-Alarm Testing | 4/2/2008 | 4/2/2008 | 4/2/2008 | P | PART |
Forrest France
|
|
|
testing of connetion between hood and fire alarm completed, no other fire alarm testing completed.KR
|
INSP-Final Inspection | 3/31/2008 | 4/1/2008 | 4/1/2008 | P | CANC |
Forrest France
|
|
|
Wrong permit called in.This job is not ready.KR
|
Issue and Print Permit | | | 1/3/2008 | | DONE |
|
|
|
|
Telephone call | | | 1/2/2008 | | DONE |
|
|
|
left message w allie for matt casey at ###-#### - permit ready and no fees due
|
Permit Ready to Issue | | | 1/2/2008 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 12/28/2007 | | 12/31/2007 | | PASS |
|
|
|
12/31/2007 16:05:36 MWT - activity updated through activity FIRA22 from case FIR07-01053.
|
Alarm Plan Check | 12/31/2007 | | 12/31/2007 | | PASS |
Michael Timmerman
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/31/2007 | | DONE |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 12/31/2007 | | 12/31/2007 | | DONE |
Patricia Smith
|
|
|
|
Case Summary | | | 12/28/2007 | | |
|
|
|
|
Application received | | | 12/28/2007 | | |
|
|
|
|