Permit Information
Permit NumberFIR07-01054
StatusFinaled
Name UNITED FIRE PROTECTION LLC
Site Address 936 S VISTA AVE
Project NameVISTA VILLAGE
Customer Number 
ePlanReview 
Description
Add (19) New Tyco SSP's @ New Grid Ceilings, & demo (18) existing SSU's. IFC Occupancy Group = B, TI Space sq footage = 1,649 ft/2. "No" new hydraulic calc's have been provided as part of this Quick Permit Application. IFC Construction Type = V-B TI Space is sprinklered in accordance with the IFC 2003 Edition and teh NFPA-13, 2002 Edition. Original Sprinkler System installed by Viking Sprinkler under FIR #: 06-00294.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/19/20082/19/20082/19/2008PPASS
DetailsForrest France
Corrections are finished, fire sprinkler permit finaled.
INSP-Sprinkler Rough-in2/13/20082/13/20082/13/2008PPART
DetailsForrest France
Verified corrections noted at the previous inspection are compliant, overhead modifications are approved for cover at the drop ceilings, discussed need for a current annual inspection to be provided for the existing fire sprinkler system prior to building permit final.
INSP-Sprinkler Rough-in2/12/20082/12/20082/13/2008PDEFR
DetailsForrest France
Duplicate inspection request.
INSP-Sprinkler Rough-in2/8/20082/8/20082/8/2008PFAIL
DetailsTroy Cobbley
Additional upright sprinkler protection is required in the combustible concealed space due to the new duct work obstructing the spray of the existing upright fire sprinklers. Also the existing riser needs to have a current inspection.
Issue and Print Permit  1/15/2008 DONE
Inspection Record Card- Fire1/14/2008 1/14/2008 DONE
DetailsCathy Brown
Telephone call  1/14/2008 DONE
lft ms with secretary ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  1/14/2008 DONE
Telephone call  1/11/2008 DONE
Ben Chavez called to check on status of quick permit sprinkler review for this project. This plan was inadvertantly picked up by the contracted fire sprinkler plan reviewer, Johnson Consulting. Contacted Johnson Consulting and confirmend that this project needs to be expedited ASAP, as it is a quick permit.
Case Summary  12/31/2007 DONE
Application received  12/31/2007  
Pending Assignment by SAM12/31/2007