Miscellaneous action | | | 5/8/2009 | | DONE |
|
|
|
plans taken to records to scan
|
INSP-Final Inspection | 12/9/2008 | 12/11/2008 | 12/11/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 12/8/2008 | 12/9/2008 | 12/9/2008 | P | FAIL |
Troy Cobbley
|
|
|
All of the smoke detectors and manual pull stations have been tested including phone line troubles and battery tourbles. Phone line one appears to have a problem. Audio/visuals need to be tested as well as end of line voltage. A map at the facp is required.
|
INSP-Final Inspection | 12/5/2008 | 12/8/2008 | 12/8/2008 | P | FAIL |
Troy Cobbley
|
|
|
This inspection turned into a first floor walk through/conference. All of the first floor wing smoke detectors are overspaced, a smoke detector in the common are needs to be relocated closer to the double doors to the wing and visuals are overspaced. Locations are marked on the plans. No testing was performed.
|
FIR-Aging Inspection | 11/24/2008 | 11/24/2008 | 11/26/2008 | | NR |
Troy Cobbley
|
|
|
Per Darcy the work for this project is in progress.
|
Issue and Print Permit | | | 8/15/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/14/2008 | | DONE |
|
|
|
Spoke to Stephen regarding the circuit lengths and voltage drops. There are a few areas that the candelas need to be increased and the voltage drops already seem very close to 10%. He stated that he will reevaluate the voltage drops based on the device increases and will call me back on Monday to tell me if we need to send the drawings back to design (thus rejecting the plans) or if the voltage drops will meet requirements and we can continue on with the review.
|
Telephone call | | | 8/14/2008 | | DONE |
|
|
|
Called High Country and left a message to call me back and that the review would not be complete until Monday when I get the information requested from the designer.
|
Telephone call | | | 8/14/2008 | | DONE |
|
|
|
Steven called me to let me know he re-evaluated the voltage drops, and stated he his completely certain that even after adding devices and increasing candelas that the end of line voltage drops will not exceed a 10% drop.
|
Alarm Plan Check | | | 8/14/2008 | | PASS |
|
|
|
See redlines on drawings and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/14/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/14/2008 | | 8/14/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/14/2008 | | DONE |
|
|
|
left vm for high country alarm at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/14/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/8/2008 | | |
Stephanie L. Cobbley
|
|
|
Received application, two copies of submittal binder and plan sheets 2 of 20, FA-1, FA-2, FA-3, FA-4, FA-5; taken to Fire Review
|
Plan assigned to (Stephanie) | 8/8/2008 | | 8/8/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Miscellaneous action | | | 7/25/2008 | | DONE |
Tisha Gallop
|
|
|
picked up denied plans
|
Miscellaneous action | | | 7/23/2008 | | DONE |
|
|
|
Faxed review comments to High Country Alarm
|
Alarm Plan Check | | | 7/23/2008 | | FAIL |
|
|
|
Pick up redlined plans and submittals at front desk
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/23/2008 | | DONE |
|
|
|
Plans taken to front desk
|
Plan resubmittals received | | | 7/14/2008 | | |
Stephanie L. Cobbley
|
|
|
Received application, three copies of product data and sheets FA-1, FA-2, FA-3, FA-4, FA-5; taken to fire review.
|
Miscellaneous action | | | 2/6/2008 | | DONE |
|
|
|
released failed plans to High Country Alarm. Ok to release per Rodney Gilroy (facility mgr. from Chateau De Boise).
|
Miscellaneous action | | | 1/8/2008 | | DONE |
|
|
|
Fax copy of fire alarm review to applicant Larry Ward Holiday Retirement. ###-#### copy Rodney Gilroy Chateau De Boise. ###-####
|
Telephone call | | | 1/8/2008 | | DONE |
|
|
|
Called - Chateau de Boise - ###-#### Let Rodney Gilroy know I received the fire alarm plans from his coperate office. I also let him know that a quick glance would probably have to fail the fire alarm submittals due to several code problems.
|
Miscellaneous action | | | 1/8/2008 | | DONE |
|
|
|
Failed plan set taken to permit desk for return.
|
Telephone call | | | 1/8/2008 | | DONE |
|
|
|
left vm for larry ward at ###-#### - permit needs to be picked up and resubmitted
|
Alarm Plan Check | 1/7/2008 | | 1/7/2008 | | FAIL |
Michael Timmerman
|
|
|
Fire Alarm Review 1st
|
Application received | | | 1/4/2008 | | |
|
|
|
|
Plan assigned to (Mike) | 1/4/2008 | | 1/4/2008 | | DONE |
Michael Timmerman
|
|
|
Plans Received via Courrier
|