Case Summary | | | 12/9/2008 | | |
|
|
|
|
Miscellaneous action | | | 6/4/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 3/13/2008 | 3/14/2008 | 3/14/2008 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 3/10/2008 | 3/12/2008 | 3/12/2008 | P | FAIL |
Troy Cobbley
|
|
|
Provide monitor module for the existing duct smoke detector and relocate the new duct smoke detector to the return side of the hvac unit. Location is marked on the plans. Also provide the monitoring station test reports for review.
|
Issue and Print Permit | | | 1/25/2008 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 1/7/2008 | | 1/18/2008 | | PASS |
Michael Timmerman
|
|
|
1/18/2008 10:40:11 MWT - activity updated through activity FIRA22 from case FIR08-00014.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/18/2008 | | DONE |
|
|
|
Ready for Issue
|
Miscellaneous action | | | 1/18/2008 | | DONE |
|
|
|
Received Revised Battery Calculations from ADT via Fax. Plans Issued.
|
Inspection Record Card- Fire | 1/18/2008 | | 1/18/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/18/2008 | | DONE |
|
|
|
t/c w dave whiting at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/18/2008 | | DONE |
|
|
|
|
Alarm Plan Check | 1/14/2008 | | 1/14/2008 | | PASS |
Michael Timmerman
|
|
|
Fire Alarm Review 1st - Revised Battery Calculations Received VIA Fax 1-16-2008 Permit Issued
|
Telephone call | | | 1/14/2008 | | DONE |
|
|
|
Called Dave Whiting at ADT, told Dave that battery calculations did not add up and I need how he derived his NAC alarm current. Told Dave I would hold plans in pending waiting for information for 24hrs.
|
Case Summary | | | 1/7/2008 | | |
|
|
|
|
Application received | | | 1/7/2008 | | |
|
|
|
|