INSP-Final Inspection | 7/22/2008 | 7/22/2008 | 7/22/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Final Inspection | 7/18/2008 | 7/18/2008 | 7/18/2008 | P | FAIL |
Troy Cobbley
|
|
|
Provide locks and/or chains for both of the PIV's and I need verification that the intake pipe in the new storage tank is at the correct height.
|
INSP-Sprinkler Rough-in/Hydro | 7/16/2008 | 7/17/2008 | 7/17/2008 | P | PASS |
Troy Cobbley
|
|
|
The underground hydro test passed and the underground flush passed.
|
CHANGE STATUS TO (ISS) | | | 7/8/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 6/17/2008 | | |
Stacey Carlson
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 5/7/2008 | 5/8/2008 | 5/8/2008 | A | PASS |
Troy Cobbley
|
|
|
24 hour air test passed
|
INSP-Sprinkler Rough-in/Hydro | 5/6/2008 | 5/7/2008 | 5/7/2008 | A | PART |
Troy Cobbley
|
|
|
24 hour air test started at 8:30am with 45 psi on the guage.
|
INSP-Sprinkler Rough-in/Hydro | 5/2/2008 | 5/6/2008 | 5/6/2008 | A | PASS |
Troy Cobbley
|
|
|
Above ground hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 5/1/2008 | 5/2/2008 | 5/2/2008 | P | FAIL |
Troy Cobbley
|
|
|
Above ground hydro test failed due to leaks. To be rescheduled for monday.
|
INSP-Sprinkler Rough-in | 4/3/2008 | 4/4/2008 | 4/4/2008 | P | PASS |
Troy Cobbley
|
|
|
The remaining underground piping is ok to cover.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/28/2008 | | DONE |
|
|
|
|
Telephone call | | | 3/28/2008 | | DONE |
|
|
|
t/c w chris wilson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/28/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/28/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/28/2008 | | 3/28/2008 | | DONE |
Patricia Smith
|
|
|
|
Sprinkler Plan Check | 1/14/2008 | | 3/27/2008 | | PASS |
|
|
|
approved w/ conditions
|
Sprinkler Plan Check | 3/25/2008 | | 3/25/2008 | | DONE |
Sam Rogers
|
|
|
Engineering evaluation of the new tank and existing well supply by J. L. O'Neal, P.F.E. was reviewed by D. Hanneman, Fire Marshal, and found acceptable as an approved alternative design for this specific temporary situation. Signed documents attached to this case and faxed back to architect.
|
Plan resubmittals received | | | 3/19/2008 | | DONE |
|
|
|
Letter from architect and PE evaluation of tank and well pump water supply
|
Telephone call | | | 2/4/2008 | | DONE |
|
|
|
Confirming my telcon with Gregg Patrick, TVFP, ph: ###-####. TVFP needs to start installation of UG piping between the proposed tank and the building within two weeks. I suggested they submit plans and application for an Underground Fire permit. We will not release approved overhead sprinkler plans until we have approved the fire protection water tank plans and confirmed the proposed water supply curve, to be used for the overhead sprinkler design. I explained the fire tank plans need to be designed to NFPA 22 Standards and be stamped by a State licensed PE qualified in FP design. Gregg offered to work with the contractor to get the proper plans and design information prepared and submitted under a separate FIR permit, since the tank installation is not a part of TVFP's contract.
Regards,
Sam
|
Case Summary | | | 1/14/2008 | | |
|
|
|
|
Application received | | | 1/14/2008 | | |
|
|
|
|
Pending Assignment by SAM | 1/14/2008 | | | | DONE |
|
|
|
Plans sent to BJ.
|