Permit Information
Permit NumberFIR08-00045
StatusFinaled
Name WESTERN STATES FIRE PROTECTION
Site Address 512 N 8TH ST
Project NameST. MICHAEL'S
Customer Number 
ePlanReview 
Description
11/13/08 Revised FIR Scope of Work:
These plans were submitted as an As-Built of the project Scope of Work:
(ST. MICHAEL'S EPISCOPAL CHURCH - BISHOP TUTTLE HOUSE AND SITE WORK - PHASE I) The Bishop Tuttle House and the Funsten House will be fire sprinklered for story increase and for code trade-offs. To remodel the 3,424 square foot basement and 3,616 square foot 1st story of the Bishop Tuttle House of St. Michael's Episcopal Church. A 950 square foot 1st story mezzanine addition will also be constructed. The Bishop Tuttle House and the Funsten house will be fully fire sprinklered in conjunction with this permit. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. The combination of parcels must be completed before this permit is given a final. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD07-01784. This permit is not attached to any other permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/13/2010 DONE
Sent to records for scanning.
INSP-Final Inspection10/2/200910/5/200910/5/2009APASS
DetailsForrest France
Fire sprinkler permit approved for final status.
Pending Assignment by SAM1/17/2008 9/21/2009 DONE
DetailsTisha Gallop
9/21/2009 16:59:42 LEG - activity updated through activity FIRA158 from case FIR09-00578.
INSP-Final Inspection9/14/20099/14/20099/15/2009PNR
DetailsForrest France
Work incompleted on correction notice items.
INSP-Final Inspection8/12/20098/14/20098/14/2009AFAIL
DetailsForrest France
See stamped plan set for locations in need or revision including overspaced heads at the kitchen 103, one overspaced head at the basement hallway, one blocked upright at a closet 1st floor, need to provide access to three locked rooms and the elevator pit, one sw head at the stairway needs the travel cap removed, escutcheons missing at three heads.
INSP-Sprinkler Rough-in/Hydro2/23/20092/23/20092/23/2009PPASS
DetailsTroy Cobbley
Hydro Test Passed for wet and AnitFreeze
INSP-Sprinkler Rough-in/Hydro2/20/20092/23/20092/23/2009AFAIL
DetailsTroy Cobbley
Hydro test was not even started due to the fitter finding a leak.
INSP-Final Inspection2/19/20092/19/20092/19/2009PNR
DetailsForrest France
casey - please call 1/2 hr prior Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro1/21/20091/22/20091/22/2009PPART
DetailsForrest France
Verified resubmitted plans for installation changes at the 1st floor area funsten house, okay for ceiling cover as initialed and annotated with today's date, noted flex couplings to be provided at the floor penetration for the 4" main.
Issue and Print Permit  11/18/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  11/17/2008 DONE
DetailsCathy Brown
Inspection Record Card- Fire11/17/2008 11/17/2008 DONE
DetailsCathy Brown
Telephone call  11/17/2008 DONE
DetailsCathy Brown
lft vm with tim ###-#### that permit and fees are ready are to be picked up
Permit Ready to Issue  11/17/2008 DONE
DetailsCathy Brown
Sprinkler Plan Check11/4/2008 11/13/2008 PASS
Details
As-Built Plans are approved by Bryan Johnson
Plan resubmittals received  11/4/2008  
Plan mod Rec'd by Fedex; rec'd one copy of application and 4 copies of submittal packet and 4 copies of sheets FP-1, FP-2, FP-3; taken to fire review
Sprinkler Plan Check10/20/2008 10/31/2008 FAIL
Details
These plans were denied due to missing information. Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set of plans will be maintained for five working days.
Plan resubmittals received  10/20/2008  
Plan Mod, rec'd united water flow sheet, application, 2 copies of submittal packet and 4 copies of sheets FP-1, FP-2, FP-3; taken to fire review
Sprinkler Plan Check9/26/2008 10/14/2008 FAIL
Details
These plans were denied due to non correlation between the plans and remote area calculation summary's submitted. Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set of plans will be maintained for 5 working days.
Plan assigned to (SAM)9/26/2008 9/26/2008 DONE
DetailsSam Rogers
Plan resubmittals received  9/26/2008  
DetailsBarbara Stitt
Recieved 1 cover transmittal, 1 cover letter regarding as built conditions, 1 application, 2 copies of water test information, 4 copies of as built fire protection drawings (sheets FP1-3), 2 copies of 2 sets of hydraulic cover sheet & calculations via mail delivery and put in fire inbox///9-26-08 BAS
INSP-Sprinkler Rough-in8/29/20088/29/20088/29/2008PFAIL
DetailsForrest France
On site visit to confirm notes per last inspection completed 8/19. Dry upright sprinkler coverage is overspaced or missing at several locations, noted several field modifications which will necessitate resubmitted plans matching the installation.
INSP-Sprinkler Rough-in8/28/20088/28/20088/28/2008PFAIL
DetailsForrest France
Chris- call 30 min prior to going to meet Phone #: ###-#### No access yet provided to inspect dry uprights as noted per last site visit completed 8/19, inspection rescheduled per phone conversation.
Meeting  8/28/2008 DONE
Walk-in meeting with Laura Bachelor, Cooperative Preschool at St. Michaels (###-####) inquiring if the City had ordered her preschool to vacate the building as a result of the recent "failed" sprinkler inspection. I indicated the PDS/Fire Division had not done so and that per my discussion with Carl Westfall, (building plan reviewer), the City had not required the building to be vacated during the Building permit construction period. I indicated it may be necessary to vacate the area for practical purposes to accommodate the additional sprinkler work and related construction work but that decision would be the building owner's, not the City's in this case.
INSP-Sprinkler Rough-in/Hydro8/18/20088/19/20088/19/2008AFAIL
DetailsTroy Cobbley
Resubmittals are needed showing the upright heads being changed to pendant heads, added upright heads in the daycare/remote area, and all of the added pendants in the closets. The entire space above the ceiling, in the daycare, will need to be covered with sprinklers or a code based solution provided. Access shall be provided to view the dry upright sprinkler heads. The uprights have been deleted from the corridors but there is exposed wood above the ceilings in the corridors. Reducing fittings have been used and are not allowed per NFPA 13 unless the exception is met.
INSP-Sprinkler Rough-in/Hydro6/12/20086/12/20086/12/2008PNR
DetailsForrest France
Jerry Phone#: ###-####
INSP-Sprinkler Rough-in5/30/20085/30/20085/30/2008PPART
DetailsTroy Cobbley
This inspection was for the installation of the 4" PIV. The PIV can be covered. I let the contractor know that it would be a good idea to get the conduit for the tamper switch installed prior to bury.
INSP-Sprinkler Rough-in/Hydro5/12/20085/13/20085/13/2008AFAIL
DetailsForrest France
See approved plan set for attic area clouded per inspection completed today-noted one hanger at the 4" main to be reattatched, one missing hanger, and one upright head blocked by and adjacent truss web.
INSP-Sprinkler Rough-in5/12/20085/12/20085/12/2008PNR
DetailsForrest France
jerry Phone #: ###-####
INSP-Sprinkler Rough-in5/1/20085/1/20085/5/2008PPART
DetailsForrest France
OH fire sprinkler okayed for cover at the hard lid intermediate landing adjacent to the east stairway.
INSP-Sprinkler Rough-in4/15/20084/15/20084/16/2008PPART
DetailsForrest France
See approved plans for hard lid restroom areas at the basement okayed for cover.
INSP-Sprinkler Rough-in4/3/20084/4/20084/4/2008APART
DetailsForrest France
Ok to cover main entance of Bishop tuttle house room# 109 stairwell.KR
INSP-Conference4/1/20084/1/20084/1/2008PDONE
DetailsTroy Cobbley
Jerry wanted to know precedures for getting some of the sprinkler piping covered. I notified him we could do partial rough-in sprinkler inspections.
PLANS/APPL TAKEN TO FRONT DESK  3/21/2008  
Inspection Record Card- Fire3/21/2008 3/21/2008 DONE
DetailsCathy Brown
Telephone call  3/21/2008 DONE
lft vm with mikc ###-#### and tlk with tim ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  3/21/2008 DONE
Issue and Print Permit  3/21/2008 DONE
Sprinkler Plan Check3/13/2009 3/19/2008 PASS
Details
These plans were approved with conditions by Bryan Johnson
Plan resubmittals received  3/13/2008  
received application and five sets of plans with submittal information; taken to fire review
Telephone call  2/11/2008 DONE
Call from Ben Hill, regarding status of Fire Sprinkler plan review. plans have not been logged back into city, as of yet. Log book indicates a note stating "hold". Reffered Mr. hill to Johnson Consulting for explanation.
Application received  1/17/2008  
Sprinkler Plan Check1/17/2008 2/6/2007 FAIL
Details
These plans were denied due to missing and incorrect information provided. Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set will be maintained for five working days