Miscellaneous action | | | 6/4/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 2/15/2008 | 2/15/2008 | 2/15/2008 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Final Inspection | 2/8/2008 | 2/8/2008 | 2/8/2008 | P | PART |
Forrest France
|
|
|
Pending aging fire alarm permit work on the system.
|
INSP-Final Inspection | 2/7/2008 | 2/7/2008 | 2/7/2008 | P | PASS |
Forrest France
|
|
|
Corrections made per last inspection. KR
|
INSP-Final Inspection | 2/6/2008 | 2/6/2008 | 2/6/2008 | P | FAIL |
Forrest France
|
|
|
Strobes in the men's and woman's restrooms did not function.All other devices on 2nd floor worked correctly. KR
|
Issue and Print Permit | | | 1/29/2008 | | |
|
|
|
|
Plan assigned to (Mike) | 1/17/2008 | | 1/28/2008 | | PASS |
Sam Rogers
|
|
|
1/28/2008 15:42:17 SLR - activity updated through activity FIRA22 from case FIR08-00046.
|
Plan assigned to (Mike) | 1/24/2008 | | 1/28/2008 | | PASS |
Sam Rogers
|
|
|
1/28/2008 15:42:17 SLR - activity updated through activity FIRA22 from case FIR08-00046.
|
Plan resubmittals received | | | 1/28/2008 | | |
|
|
|
received three copies of info on existing system and sheets FA0.0, FA1.0, FA1.1, FA2.2; taken to fire review
|
Alarm Plan Check | 1/28/2008 | | 1/28/2008 | | PASS |
Sam Rogers
|
|
|
Plans approved subject to annotations. To expedite review, no review comments were written; final approval subject to satisfactory inspection.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/28/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/28/2008 | | 1/28/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/28/2008 | | DONE |
|
|
|
left message w tricia for david uli at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/28/2008 | | DONE |
|
|
|
|
Case Summary | | | 1/28/2008 | | |
|
|
|
|
Plan assigned to (SAM) | 1/24/2008 | | 1/24/2008 | | FAIL |
Sam Rogers
|
|
|
Review comments faxed to Allied General. Fire alarm plans and issued building plans reviewed in person with Ken Webster prior to review.
|
Permit VOIDED | 1/18/2008 | 1/18/2008 | 1/18/2008 | | DONE |
Michael Timmerman
|
|
|
Permit Voided. Duplicate Permit - This same paln was received and approved 1/14/2008 by M2 Automation & Control Services.
|
Application received | | | 1/17/2008 | | |
|
|
|
|